Common adsorbents studied to remove volatile organic compounds (VOCs) from indoor air can release previously adsorbed VOCs back into the indoor space when the adsorbent is saturated or if the VOC concentration fluctuates. A durable adsorbent with a continuous regeneration strategy could prevent this recontamination of the indoor air and reduce adsorbent disposal waste. A deeper understanding of the adsorption and desorption behavior of VOC adsorbents is needed to create an efficient regeneration strategy. This study investigated the adsorption and thermal desorption behavior of toluene on two different adsorbents, (1) a zeolite-based adsorbent and (2) an activated carbon fiber (ACF) felt. Consistent adsorption behavior across a series of toluene concentrations was used to experimentally determine effective adsorption capacity. When the cumulative adsorption between thermal regeneration steps was maintained below the maximum effective capacity with 0% breakthrough, the zeolite-based adsorbent was found to effectively minimize passive desorption. The impact of regeneration feed conditions, such as inert, oxidizing, humidified air, on thermal desorption was examined. These conditions influenced desorption of the zeolite-based adsorbent but had minimal impact on the ACF felt adsorbent, which would lead to different regeneration schedules and methods for applications in buildings' heating, ventilation, and air conditioning (HVAC) systems.
Environmental significanceThe use of adsorbents for removal of volatile organic compounds (VOCs) from indoor air should prevent passive desorption back into indoor space when concentrations drop or are low. Integration of the adsorbent into the building ventilation system would be further improved if in-line regeneration of the adsorbent under mild conditions is possible. An understanding of adsorption capacity and desorption conditions are needed to design effective integration. To assist in this design related to the potential adsorbent placement locations in the intake or recirculated air flow and how often the adsorbent may need to be bypassed for regeneration, this paper investigates the maximum adsorption without passive desorption and the environmental conditions required for regeneration for two different types of adsorbents. |
Applying air cleaning devices in building heating, ventilation, and air conditioning (HVAC) systems can be an effective and energy efficient approach to control VOCs by reducing the need for outdoor air ventilation.8 As allowed by the IAQ Procedure in ASHRAE Standard 62.1 “Ventilation and Acceptable Indoor Air Quality”, the outdoor air intake rate can be determined by meeting the concentration limits of design compounds that contain 11 VOCs in replacement of a prescriptive rate based on space and occupancy.9 To efficiently and effectively improve indoor air quality without energy wasting due to outdoor-air exchange, identifying and optimizing VOC removal technologies that are ready for application in buildings is critical.
VOC abatement methods can be divided into two categories – recovery and conversion/destruction – depending on whether VOCs are trapped or converted into different compounds, respectively.10 Adsorption is a highly promising trapping method, known for its relatively low cost and proven effectiveness in achieving high removal rates and fewer byproducts compared to destruction methods such as photocatalytic oxidation and plasma catalysis.10,11 The most popular materials for VOC adsorption are activated carbon and zeolites.12 Filters containing pure granular activated carbon (GAC) have been reported to maintain over 90% efficiency when challenged by 4 ppm toluene for 30 h.13 Packed bed reactor evaluation of toluene removal by GAC have shown adsorption capacities ranging from 350 to 600 mg g−1 depending on the bed depth, challenge concentration, and flow rate.14 Compared to GAC, activated carbon fiber (ACF) that can be made into cloth or felt has a higher adsorption efficiency and is easier to regenerate.15,16 When tested under identical conditions using the same weight of the adsorbent for removing toluene, the breakthrough time for ACF (45 min) was nearly two times longer than GAC (25 min). Zeolites are another adsorbent suitable for VOCs due to their high surface area, pore volume, and thermal stability.17 One study demonstrated toluene adsorption capacities ranging from 80 to 210 mg g−1 for different types of zeolites.18 The referenced absolute GAC, ACF and zeolite capacities are not directly comparable due to differences between the referenced works. Nevertheless, these ACF and zeolite adsorption capacities suggest them to be good candidates for cleaning VOCs from indoor air.
Several regeneration methods have been applied to ACF and zeolite adsorbents to facilitate continuous use. Following toluene saturation of ACF cloth, electrothermal heating for 30 min at 145 °C was found to recover 75% adsorption capacity in the first adsorption–desorption cycle but no further loss in capacity occurred over the following four cycles.19 Another study used ACF cloth to adsorb and desorb a mixture of VOCs below 50 ppb in a cyclic process and reported greater than 60% toluene removal efficiency was maintained over five, 12 h adsorption – 15 min, 150 °C regeneration cycles. Circulating a DC current through the ACF cloth was used in this study to heat the ACF cloth to 150 °C during the 15 min regenerations.8 A similar study reported passing a DC current through a ACF cloth for 60 min to investigate desorption temperature impacts and found that 150 °C led to more complete desorption of toluene compared to 75 °C and 100 °C, while increasing the temperature higher to 200 °C did not provide any further improvement.15 A study on regeneration of zeolite adsorbents found that more toluene was desorbed by microwave heating at 500 W for 10 min (the final temperature of the adsorbents varied from 60 to 184 °C depending on the type of the zeolite adsorbent and gas stream) than conventional heating to 300 °C at a heating rate of 5 °C min−1 using an electric furnace.17 A recent study demonstrated that a 85% toluene adsorption capacity could be recovered over five adsorption–desorption cycles on zeolites by increasing temperature from 25 °C to 180 °C during desorption.18
The main challenges to real-world application of ACF and zeolites to improve indoor air quality are degrading adsorption efficiency over time and passive or uncontrolled VOC desorption. While ACFs and zeolites have high toluene adsorption capacities, that capacity fills via an “S” shaped breakthrough curve;15,18 efficient initial adsorption by highly active and/or accessible adsorption sites, followed by progressively degraded adsorption due to fewer active and/or accessible sites. The high adsorption capacity but slow rate of adsorption, in some applications, may require that the adsorbent be replaced before the maximum adsorption is reached to prevent the concentration downstream of the adsorbents from increasing to undesirable levels in the breathing zone of building occupants. Additionally, the adsorbent itself could become a VOC source if it allows passive VOC desorption when exposed to airflows with relatively low VOC concentrations. It was found that 40.9% of toluene previously adsorbed on GAC was passively desorbed when exposed to Helium for 2 h.20 This reversibility of adsorption in the presence of concentration dynamics was recently reported for benzene on GAC and occurred even when the GAC was far from saturation.21 The combined issue of slow adsorption rates and passive desorption may be addressed by regenerating the adsorbents on-site on a regular basis to both effectively clean air and reduce waste caused by using non-reusable adsorbents. For optimal VOC removal system, it is important to determine the regeneration frequency and conditions and to quantify the fractional or effective capacities that can be recovered.
While literature exists describing the adsorption–desorption behavior and regeneration of adsorbents for VOC removal, the information on relating the breakthrough and adsorption capacity at high contaminant concentrations to lower ones and the effectiveness of adsorbent regeneration under varying conditions is still lacking. A systematic bench scale experimental study is needed especially for zeolites and activated carbon fibers that are highly promising for IAQ applications in buildings. The objectives of this study were to understand the performance of two distinctly different adsorbents – a zeolite-based adsorbent and an activated carbon fiber felt – in removing toluene and being regenerated for reuse if incorporated into HVAC systems. The temperature and oxidative environment impact on the regeneration process of both adsorbents along with adsorption capacity by considering passive desorption were investigated to enable the in-line regeneration at an optimal frequency, temperature and environment. Toluene was used as the VOC in this study because of its similar structure to other more hazardous aromatic hydrocarbons and has been widely used to represent VOCs in literature on the adsorption and desorption behavior of adsorbents.22–25 The toluene adsorption on the two adsorbents was studied under three challenge concentrations (60, 140, and 200 ppm) to establish the relationship between the breakthrough time and total mass challenged and determine the effective adsorption capacity of each adsorbent. The impacts of temperature (30 °C to 300 °C) and gas compositions (inert vs. oxidizing and dry vs. humidified) during regeneration were investigated to aid in future development of efficient regeneration strategies.
The 2 L washcoated monolith was degreened by SGS North America Inc. at 700 °C for 50 h using stationary engine exhaust under the recommended US Drive protocol.26 The low-temperature hydrocarbon trapping target of this zeolite-based monolith made it a compelling material to investigate as a VOC adsorbent for IAQ applications. Smaller monolith samples were cut from the front of the 2 L zeolite monolith for evaluation. The Fig. 1(A) schematic describes the macrostructure of a typical washcoated monolith. For all samples studied, the length and number of washcoated channels in the sample were used to calculate a relative volume of monolith for sample-to-sample comparisons. Adsorption results were normalized to the estimated mass of the zeolite-based adsorbent (MZB). The washcoated adsorbent was calculated from the number (Nch) and length (Lch) of monolith channels used and the number of channels per cross-sectional area of the 400 cpsi monolith (Ach, 0.620 ch mm−2) according to eqn (1).
![]() | (1) |
![]() | (2) |
![]() | ||
| Fig. 2 Schematic of bench reactor layout used for measuring adsorbent's toluene adsorption and desorption behavior from a contaminated air flow. | ||
Toluene concentrations were measured with a MKS MultiGas 2020, 5 Hz fast-response FTIR using the “Aromatic as C7” measurement from a MKS calibrated analysis method. All FTIR data was measured at a 1 s resolution. To dampen measurement noise at low FTIR concentration readings, the 1 s sampling measurements were smoothed using a 15 s running average for final graphing of the toluene breakthrough data; all prior data processing was done directly to the 1 s sampling measurements. The gas-feed toluene concentration was controlled by adjusting the fractional N2 flow to the toluene bubbler and confirmed by bypassing measurements prior to evaluation. Once the target feed toluene concentration was confirmed, the gas flow was routed through the quartz tube allowing the toluene concentration downstream of the adsorbent to be continuously measured. The toluene in the synthetic air feed could be switched on and off using a heated 4-way switching valve which sent the equivalent N2 flow to the gas mixture when toluene-free air feed was required.
Adsorption studies were performed for each adsorbent at 30 °C using different toluene concentrations in the feed air flow; the specific toluene concentration used for a given measurement is referred to as the “challenge” concentration. Breakthrough curves use the upstream (feed) and downstream (post adsorbent) toluene concentrations to show the fraction of the toluene (Tb%) that breaks through the adsorbent (i.e. not adsorbed) over the duration of a toluene challenge study according to eqn (3). Where Cfeed was the toluene challenge concentration measured during sample bypass, while C was the toluene concentration measured downstream of the adsorbent.
![]() | (3) |
Toluene mass adsorption rates, ṁads, were calculated from FTIR concentrations according to eqn (4). Where MW was the molecular weight of toluene, Qtot was the total gas flow rate and Vmol,0°C was the molar volume of gas at STP (0 °C). The toluene mass feed rates, ṁfeed, were calculated from adsorbent bypass measurements (Cfeed) taken prior to the challenge study and calculated according to eqn (5).
![]() | (4) |
![]() | (5) |
Using the FTIR measurements of the downstream toluene concentration, C, allowed the ṁads to be calculated at a 1 s resolutions. After accounting for this one second interval, a continual summation according to eqn (6), where ṁ is ṁads from eqn (4), provides the toluene mass adsorption data as a cumulative adsorption, Δmads.
![]() | (6) |
Prior to each of the three repeated adsorption cycles, the adsorbent was pretreated in the clean synthetic air flow described above (including H2O, CO2, O2 and N2) at 300 °C for 10 min and then cooled to the adsorption challenge test temperature all in the absence of toluene. Following each adsorption challenge study, the toluene dopant was removed from the synthetic air feed while the air flow continued passing through the adsorbent for 5 min before preparing the reactor for a desorption step to regenerate the adsorbent for a repeated adsorption cycle and provided information about reversible toluene adsorption at the 30 °C adsorption temperature. To prepare the sample for the next toluene challenge concentration measurement, the tube furnaces were ramped from 30 °C to 300 °C at 5 °C min−1 to heat the inlet air and adsorbent sample to release the adsorbed toluene under a process known as temperature program desorption (TPD). The toluene desorption rates were measured by the FTIR and converted to mass desorption rates (ṁde) and cumulative mass desorbed (Δṁde) according to eqn (6) and (7) directly from the downstream toluene concentrations measured after toluene was removed from the feed and during the TPD, where ṁ in eqn (6) is ṁde from eqn (7).
![]() | (7) |
Each adsorbent sample was tested over three cycles of adsorption and desorption. The TPD enabled reproducible evaluation of the adsorbent's toluene adsorption performance, and all adsorption results are presented as averages across the three adsorption cycles, with error bars indicating the minimum/maximum values.
In addition to enabling repeated adsorption cycles, the TPD studies were used to investigate the regeneration potential of the adsorbents to extend their in-use application and useful life. Since reproducible TPD results had already been established during our pilot studies for these adsorbents, the impact of the oxidative environment on adsorbent regeneration was studied up to 300 °C using a different environment after each of the three adsorption cycles. For each toluene challenge concentration, the cycle 1 TPD was run in an inert N2 only feed, the cycle 2 TPD was run in a dry air feed containing 20% O2; the cycle 3 TPD contained the same humidified air feed used for all the adsorption cycles (42% RH at 30 °C). A full humidified air feed was introduced at 300 °C for 10 min after all TPD ramp cycles to ensure complete removal of toluene.
![]() | ||
| Fig. 3 Adsorption isotherm of toluene (dry) on zeolite-based (A) and ACF-1600 (B) adsorbents. The capacity was normalized by absorbent mass. Error bars indicate the min and max range of the data. | ||
The average dry toluene adsorption for three ACF adsorbent samples, normalized by MACF, is shown in Fig. 3(B). The adsorption of toluene on ACF-1600 exhibits Type I isotherm,27,28 where a significant onset absorption capacity of 372 mg g−1 was observed at 10% P/P0. The substantial onset-adsorption at low P/P0 implies that toluene molecules can be adsorbed through micropore filling despite the lower partial pressure.29 Further increasing of the toluene P/P0 provided little increase in adsorbed capacity, which maxed out at 444 mg g−1 at 60% P/P0 (Δmcap,max). The toluene adsorption capacity dropped beyond that peak toluene partial pressure suggesting toluene desorption from the ACF adsorbent. As can be seen by error bars in Fig. 3(B), this phenomenon was repeatedly observed for all three toluene challenge studies. Toluene can be adsorbed on the carbon material through different potential interactions, including (1) hydrophobic effect, (2) π–π interaction, (3) hydrogen bonds, (4) van der Waals force, and (5) covalent and electrostatic interactions.10 Toluene–toluene interactions are around 11 kJ mol−1.30 Physical adsorption mechanisms like van der Waals forces and hydrophobic binding forces are relatively weak, and usually on the order of 10 kJ mol−1 and 5 kJ mol−1,30 respectively. When toluene P/P0 is high, the toluene adsorbed through such weak interactions could desorb due to the stronger toluene–toluene interactions. This could be the origin of the decreasing toluene adsorption observed in Fig. 3(B) at high P/P0. At 90% P/P0 of toluene the adsorption capacity dropped to 380 mg g−1 under these dry air conditions.
Fig. 4(A) shows the breakthrough times (tb%) for the zeolite-based adsorbent challenged at three different toluene concentrations (60, 140 and 200 ppm). The 60 ppm study resulted in almost no breakthrough, with an average of 1% breakthrough after 30 minutes and 4% after 70 minutes for three repeated cycles. After 60 minutes in the 200 ppm study, nearly 100% breakthrough occurred and continued for the remainder of the adsorption cycle. The 140 ppm study showed T5% halfway through the toluene adsorption cycle and just over T50% at its completion. Breakthrough time for T5% of the 200 ppm toluene challenge took 26 minutes and twice that time to reach T50%. An additional 14 minutes were needed to reach T95% at 64 minutes. The non-linear adsorption rate of toluene suggests that there may be more than one type of adsorption site with different toluene affinities. Table 1 reports the average breakthrough times (tb%) measured at 5%, 50% and 95% toluene breakthrough and the corresponding cumulative mass of toluene that had been challenged (Δmfeed,b%) at the time of breakthrough (Δmb%) according to eqn (8), where the toluene mass feed rate (ṁfeed) was calculated from eqn (5) and tb% measured can be found in Table 1. While the breakthrough times are different for different toluene challenge concentrations, the cumulative masses of toluene that had been challenged are very close.
| Δmfeed,b% = ṁfeed × tb% | (8) |
| Toluene challenge tb% (Δmfeed,b%)a | |||
|---|---|---|---|
| 60 ppm | 140 ppm | 200 ppm | |
| a 3 cycle average of toluene breakthrough mass/mass adsorbent are for sample configuration of this study with 30 °C, 42% RH air at 7.2 lpm. | |||
| Tb5% | — | 35 min (65 mg g−1) | 26 min (68 mg g−1) |
| Tb50% | — | 69 min (126 mg g−1) | 50 min (130 mg g−1) |
| Tb95% | — | — | 64 min (167 mg g−1) |
When the average toluene cumulative adsorption was correlated to the mass of toluene challenged, as shown in Fig. 4(B), the results of the three challenge concentrations collapsed to a single adsorption efficiency curve. While cumulative mass adsorption was derived at every second of the transient adsorption data, to aide in visual comparison between the different challenge concentrations in the Fig. 4(B) graph only the cumulative adsorption every 5 min is represented with markers in the plots. The strong correlation of mass adsorptions across the toluene concentrations indicated that the effective adsorption capacity for the zeolite-based adsorbent was not dependent on the VOC partial pressure, which notably differs from the adsorption isotherm study using percent challenge levels shown in Fig. 3. A 100% cumulative toluene removal efficiency was maintained, on the sample studied, up to 84 mg g−1 (±2 mg g−1, 2.5%) of cumulative toluene exposure. Once the toluene challenge exceeded 84 mg g−1, the removal efficiency began to drop until the adsorbent reached saturation. Since the 200 ppm study was the only concentration studied to reach saturation within challenge times studied, it was used to derive the average toluene saturation adsorption capacity of 125 mg g−1.
The zeolite-based adsorbent was exposed to 55 mg g−1 toluene cumulatively over the 60 ppm challenge study which resulted in only 4% breakthrough of the toluene contaminant (Fig. 4(A)) and negligible deviation from the 100% cumulative removal efficiency reference line (Fig. 4(B)) by the end of the study. In the 140 ppm and 200 ppm challenge studies, which were exposed to 130 and 184 mg g−1 cumulative toluene, respectively, a significant drop (>2.5%) in the removal efficiency began in both studies after it exceeded 84 mg g−1, as highlighted by the deviation from the 100% adsorption efficiency reference line in Fig. 4(B).
At the end of each adsorption cycle, toluene was removed from the synthetic air feed while the humidified air flow continued for at least 5 min. Reversible toluene desorption from the zeolite-based adsorbent at 30 °C adsorption temperature occurred in both the 140 ppm and 200 ppm challenge studies without heating, but not in the 60 ppm study. The occurrence of reversible toluene desorption (i.e. out-gassed) was only observed in studies that resulted in a significant drop from 100% cumulative removal efficiency suggests the presence of more than one type of adsorption site in the zeolite-based adsorbent studied. Since nothing was desorbed in the 60 ppm study, it suggested that the adsorbed toluene first adsorbs on the stronger sites before adsorbing on sites prone to passive desorption by 30 °C. The sites that more strongly adsorbed toluene would likely be between the 54 mg g−1 adsorbed during the 60 ppm study and the 84 mg g−1 adsorbed during the 140 ppm and 200 ppm study before the cumulative toluene removal efficiency dropped below 100%.
While water and toluene can compete for the same adsorption sites in the zeolite-based adsorbents, no roll-up effect on the toluene adsorption was observed in this study. A roll-up effect is typically indicated in an adsorption study when the breakthrough concentration is greater than that in the feed gas due to competitive adsorption displacing a previously adsorbed species.31 Water has been reported to more strongly interact with many adsorbents displacing previously adsorbed VOCs to cause this roll-up effect but both adsorbent properties and humidity conditions can have an impact.32,33 The adsorbents in our study were already exposed to water vapor during pretreatment, cooling and stabilization at 30 °C such that by the time toluene was introduced to the feed gas adsorptions sites which favored water would have already been saturated. The lower humidity and length of the adsorption tests in this study may have also contributed to no roll-up effect being observed.
The 60 ppm study resulted in no more than 4% toluene breakthrough resulting in nearly 100% cumulative removal efficiency during the adsorption cycles. Only 1% of the adsorbed toluene passively desorbed between the adsorption and desorption steps in that study suggesting the toluene remained securely adsorbed in the zeolite-based adsorbent until the TPD temperature rose above 70 °C in any of the feed gas environments, see orange plots in Fig. 5. In the inert and dry oxidizing environments of TPD 1 (solid lines) and TPD 2 (dashed lines), greater than 10% desorption of the toluene did not occur until the inlet air reached 90 °C followed by a steady disruption until 150 °C. In the humidified air environment of the TPD 3 (dotted lines), toluene desorption began 10 °C cooler at 80 °C and resulted in more total toluene desorbed compared to the other dry desorption environments. The competitive adsorption between water and toluene at low temperature is expected to play a role in the lower temperature desorption in humidified air. While the zeolite-based adsorbent was designed for enhanced hydrocarbon trapping near ambient temperature, water adsorption will be stronger than the toluene on many of the zeolite adsorption sites, such as the hydrophilic Brønsted acid sites. This weakening of the toluene adsorption may contribute to the lower temperature required for it to desorb in the presence of water. This is in line with water's strong competitive adsorption with toluene on zeolites.18,34
While the 200 ppm study exposed the zeolite-based adsorbent to 54 mg g−1, more toluene than the 140 ppm study, it only resulted in a slight increase in the maximum effective adsorption from 117 to 125 mg g−1, respectively. However, the 200 ppm and 140 ppm studies only maintained 100 mg g−1 (±5 mg g−1) adsorbed by the start of the TPDs. The reduction in adsorbed toluene from the maximum effective adsorption capacity indicated passive toluene desorption. This passive desorption can be seen in Fig. 5 from the drop in mass from the maximum effective adsorption capacities (symbols) and the mass remaining on the adsorbent at the start of the TPDs (line plots). In the humidified air environment of TPD 3 (dotted plots), the two higher toluene challenge studies followed similar temperature desorption profiles until about 120 °C. Therefore, under the humified air adsorption conditions of these studies, the zeolite-based adsorbent used could adsorb up to 125 mg g−1 of toluene but at least 25 mg g−1 would readily desorb in the absence of a toluene contaminant at 30 °C indicating at least 25 mg g−1 of reversible toluene adsorption capacity. Considering the drop from 100% adsorption efficiency in Fig. 4(B) occurred at 84 mg g−1 cumulative adsorption, it is probable that over an extended time at 30 °C the net reversible capacity may have increased up to 41 mg g−1 as the capacity dropped to 84 mg g−1 until exposure to higher temperatures. Since the toluene adsorption was consistent for the three repeated adsorption cycles, the differences in the amount of toluene remaining at the end of each TPD cycle in Fig. 5 may be due to toluene conversion during the TPD rather than toluene still adsorbed. Further studies are ongoing to better understand the regeneration approach, including if any conversion products are generated and correlation with the TPD environment.
| Toluene challenge tb% (Δmfeed,b%)a | |||
|---|---|---|---|
| 60 ppm | 140 ppm | 200 ppm | |
| a Toluene breakthrough masses are for sample configuration of this study with 30 °C, 42% RH air at 7.2 lpm. | |||
| Tb5% | 0.4 min (0.8 mg g−1) | 0.1 min (0.5 mg g−1) | 0.1 min (0.7 mg g−1) |
| Tb50% | — | 38 min (167 mg g−1) | 30 min (190 mg g−1) |
| Tb95% | — | 248 min (1102 mg g−1) | — |
The drop in mass from the maximum effective adsorption capacities, attained at the end of the adsorption cycles, (symbols) plotted in Fig. 7 to the mass remaining on the adsorbent at the start of the TPDs (line plots) indicates the passive desorption that occurred on the ACF adsorbent. Even though more than 50% less toluene had been adsorbed on the ACF during the 60 ppm challenge study compared to the 140 ppm and 200 ppm studies, a notable 7–8% of that adsorbed toluene passively desorbed before the start of the desorption step. Unlike the zeolite-based adsorbent, no overlap in the mass remaining on the ACF adsorbent as function of temperature was seen between the different challenge studies. The ACF adsorbent during the 140 ppm challenge study, which resulted in the greatest toluene adsorption due to exposure time, retained notably more adsorbed toluene during the TPD. These desorption results suggest that while higher temperatures may accelerate toluene desorption from the adsorbent, other properties of the ACF are significant contributors to the rate of toluene desorption.
Capacity degradation over the adsorption/regeneration cycles was not observed for either the zeolite-based or ACF felt adsorbent. The same samples were used for the 3 cycle challenge studies for all three toluene challenge concentrations. Fig. 4(A) and 6(A) show the 3 cycle averages with gray error bars to indicate the min and max values of the 3 cycles. The small deviation between the 3 cycles indicated reproducibility of the adsorption capacity for each cycle under the same toluene challenge concentration. Additionally, in Fig. 4(B) and 6(B), the same cumulative adsorption capacity for all three toluene challenge concentrations shows no degradation in the adsorption capacity under three toluene challenge concentrations. Finally, both adsorbents can withstand extended use at significantly higher temperatures than the 300 °C used in this study according to their technical data sheet, so the material structural damage due to the high temperature used in this study was not expected.
![]() | (9) |
| 400 ppb challenge concentration | 50 ppm challenge concentration | |||||
|---|---|---|---|---|---|---|
| Toluene tb%a (days) | Toluene tb%a (h) | |||||
| t5% | t50% | t95% | t5% | t50% | t95% | |
| a Breakthrough times assume 7.2 lpm flow for the same sample size/configuration presented herein and are specific to adsorbent masses used in this study. | ||||||
| Zeolite | 9.6 | 18.1 | 23.3 | 1.8 | 3.5 | 4.5 |
| ACF | (0.7h) | 9.7 | 63.9 | (< 1 min) | 1.9 | 12.3 |
These predicted results indicate that at the low 400 ppb challenge concentration, the zeolite-based adsorbent would last more than 9 days before 5% breakthrough and twice that before 50% breakthrough. After 50% breakthrough, the toluene removal efficiency drops more quickly reaching 95% breakthrough 5 days later or after 23.3 days of 400 ppb toluene exposure. The ACF breakthrough at 400 ppb shows a different trend reaching 5% breakthrough in less than an hour and 50% in under 10 days. However, 95% breakthrough over the ACF sample would take another 54 days. At the higher 50 ppm challenge concentration, breakthrough for both adsorbents would be measured on the hour scale rather than days but follows a similar trend described for the 400 ppb scenario. The zeolite-based adsorbent provides superior performance for applications requiring low VOC breakthrough. In applications where higher VOC breakthrough is tolerable, the ACF adsorbent can offer longer application times between regeneration events. Further validation of the continued adsorption linearity down to lower toluene concentration conditions is still required.
The ACF felt adsorbent showed passive desorption under all conditions studied. Its desorption rate was found to be more strongly influenced by the mass of toluene on the ACF than the temperature. While increasing the temperature helped to accelerate rate of desorption, time at the higher temperatures was still required. The slow passive desorption at room temperature and only a moderate acceleration in desorption rate at elevated temperatures may limit its potential effectiveness for some types of indoor VOC control.
On-going studies to further our understanding of the adsorbents will help to confirm the adsorption capacity at which the maximum effective toluene adsorption capacity can be trapped on the adsorbents without passive desorption and if further adsorption capacity can be accessed if upstream humidity control is available. Future studies will also focus on how much adsorption can be recovered at lower regeneration temperatures to provide reusable adsorption capacity.