Open Access Article
Qiumei Jinga,
Muhammad Ahmad Jamila,
Chunjiang Jiab,
Chong Ngb,
Wei Wangc,
Linhua Zhud,
Muhammad Wakil Shahzad*a and
Ben Bin Xu
*a
aSchool of Engineering, Physics and Mathematics, Faculty of Science and Environment, Northumbria University, Newcastle upon Tyne, NE1 8ST, UK. E-mail: muhammad.w.shahzad@northumbria.ac.uk; ben.xu@northumbria.ac.uk
bOffshore Renewable Energy Catapult, Blyth, NE24 1LZ, UK
cDepartment of Production and Automation Engineering, University of Skövde, 541 28, Skövde, Sweden
dKey Laboratory of Tropical Medicinal Resource Chemistry of Ministry of Education, Key Laboratory of Functional Organic Polymers of Haikou, Tropical Functional Polymer Materials Engineering Research Center of Hainan, College of Chemistry and Chemical Engineering, Hainan Normal University, Haikou, Hainan 571158, China
First published on 6th November 2025
Given the eruption of AI technology, the cooling requirement in data centres has drawn significant attention due to the increasing demand for data processing and storage. Indirect evaporative cooling (IEC) is a cutting-edge cooling technology with huge advantages of energy economy and environmental friendliness compared with conventional mechanical vapour compression cooling systems. Herein, we perform a levelized cost analysis (LCA) to determine the economic performance and energy consumption of the traditional mechanical vapor compression (MVC) cooling system and a novel hybrid IEC + MVC cooling system in data centre applications. A data centre model is adopted and applied in various climate zones in 10 cities from 8 countries. The results showed that the hybrid IEC + MVC system presented energy savings in all the cities, especially in Riyadh, with an energy saving of 41.3 GWh for the year. Most cities showed cost saving with the hybrid system, with London and Madrid achieving cost savings of 52–53%. All the cities showed significant CO2 reduction with the hybrid system, especially in Riyadh (23
547 tons), Jeddah (18
740 tons), and Dubai (12
432 tons). This study sheds light on the cost analysis based on levelized cost analysis (LCA) for next-generation cooling technology for data centres.
Sustainability spotlightGiven the eruption of AI technology, the cooling requirement in data centres has drawn drastic attention. Indirect evaporative cooling (IEC) is a cutting-edge cooling technology with huge advantages of energy economy and environmental friendliness compared with conventional mechanical vapour compression cooling systems. Herein, we perform the levelized cost analysis and analyse the economic performance and energy consumption of the novel hybrid IEC + MVC cooling system in data centre applications. Most cities showed cost saving with the hybrid system, with London and Madrid showed 52%–53% of cost saving. This study underpins the following SDGs: Industry, Innovation and Infrastructure (SDG 9), Responsible Consumption and Production (SDG 12), and Climate Action (SDG 13). |
The power of the current cooling systems is heavily consumed to dissipate the heat generated by the data servers. Traditional cooling systems typically rely on specialized computer room air conditioner (CRAC) units that utilize mechanical vapor compression refrigeration technology. This technology holds a dominant position in the cooling system market.4,5 IEC technology presents a significant opportunity as an alternative to traditional vapor compression cooling systems.6 The coefficient of performance (COP) of conventional vapor compression cooling systems typically ranges from 2 to 4. The energy consumption for compressor operation and reliance on refrigerants make them neither sustainable nor environmentally friendly. In contrast, IEC cooling utilizes water as the primary cooling medium, offering a sustainable and environmentally friendly option compared to conventional technologies. Additionally, IEC systems boast an impressive COP ranging from 15 to 216, which can significantly contribute to addressing net-zero targets (Table 1) in an energy saving manner. In addition, the effectiveness of the IEC varies significantly with climatic conditions, leading to substantial differences across diverse climate zones.7 The feasibility of employing IEC technology in various climatic regions has been examined in several studies. Jaber8 assessed the IEC in three cities under various climatic conditions. Balyani et al.9 and Rao and Datta10 investigated evaporative cooling performance in Iran and India under various climate zones, respectively. Sohani et al.11,12 evaluated the performance of evaporative cooling in 30 cities across the world. Based on previous studies, the results indicate that the performance of systems varies dramatically with the climate. Consequently, cost analysis is desired to provide insights into the sustainable development of the IEC by integrating geodemographic dependence.
| Features | Mechanical vapour compression | Indirect evaporative cooling |
|---|---|---|
| Market | Major market share | Growing adoption |
| COP | Low (2–4) | High (15–21) |
| Energy | Energy intensive | Energy economic |
| Environmental friendliness | Use refrigerants | Use water |
| Maintenance requirement | Regular (compressor) | Minimal (heat exchangers) |
Previous studies have exploited the energy-saving potential of IEC systems in various settings, including human thermal comfort in buildings,11,13 data centres,4,14,15 and poultry houses.16–19 Jaber,8 Navon and Arkin20 evaluated the economic feasibility and cost savings of indirect and hybrid evaporative cooling systems, respectively, highlighting significant reductions in CO2 emissions, payback periods, and electricity consumption compared to traditional systems. Existing cost evaluations of cooling systems primarily adopted life cycle analysis. Moreover, we just summarized several literature about IEC application, with some life cycle cost analysis papers in Table S1. However, the levelized cost of cooling (LCOC) metrics are underrepresented. Levelized cost analysis is particularly useful in the energy sector for comparing the economic viability of technologies that have been applied to energy systems (e.g., levelized cost of electricity) with extensive research on wind,21,22 solar energy, and energy storage systems (e.g., levelized cost of energy storage).23 The levelized cost of cooling (LCOC) metric provides a standardized and lifecycle-based economic indicator, allowing for an equivalent evaluation of various cooling systems.
Ibrahim et al.24 conducted an economic assessment of solar-assisted and conventional cooling systems for buildings in Saudi Arabia using the levelized cost annuity method. They found that the solar-assisted system had an annual energy-saving cost of ∼USD 137
944 and a payback period of about five years. Liu et al.25 analysed a solar-assisted combined heat and cold storage system using the levelized annual cost model, revealing a payback period of 17.13 years. Lee et al.26 conducted an economic assessment that compared electric heat pumps (EHP) and gas engine heat pumps (GHP) for medium space cooling using the levelized cost annuity method. The study found that EHPs are more cost-effective from the primary energy and final consumer perspectives. There remains a significant research gap in the application of indirect evaporative cooling systems within data centres, particularly from economic, environmental, and social impact perspectives.6,27 Moreover, variations in climate and economic conditions need to be considered, as they can lead to significant differences in outcomes across different countries.8–12
This study addresses the existing research gap in the field of advanced energy-saving cooling systems for data centres from both economic and environmental perspectives through the following key dimensions:
1. Employing an advanced hybrid IEC + MVC system in a realistic data centre model to explore the energy saving potential compared to the conventional MVC cooling system.
2. This research explores the economic feasibility of the employed hybrid IEC + MVC cooling system by adopting a levelized cost model to assess its lifetime financial performance in large-scale data centre applications and compares its cost performance with that of the conventional MVC system under the same operating conditions. Moreover, the reduction potential in carbon dioxide emissions associated with the electricity consumption required to operate the cooling systems is evaluated.
3. Expanded research in various climate zones with 10 cities from 8 countries by applying realistic hourly climate data for one whole year to explore the possibility and performance of hybrid and conventional systems.
![]() | ||
| Fig. 1 (a) Research path. (b) Estimated global data centres electricity consumption from 2018 to 2026.1 (c) Schematic of hybrid IEC + MVC system in a data centre.13,28–30 (d) and (e) Hybrid MVC + IEC pilot at KAUST.31 | ||
| Equipment classes | Equipment environment specifications for air cooling equipment under operation | |
|---|---|---|
| Dry-bulb temp. (°C) | Relative humidity (%) | |
| Recommended A1–A4 | 18–27 | 50–70% |
| LACOCtot = CAPCL + MCL + ELCL + CCL − SIL, | (1) |
![]() | (2) |
The levelized annual capital cost (CAPCL) involves two components: the purchase cost (ZK) and installation cost (CIN). The purchase cost (ZK) of the mechanical vapour compression system includes the cost of each component, which is the cooling tower, chiller, condenser water pump, CRAH, and chilled water pump. For the IEC + MVC system, the capital cost includes components of the MVC system and IEC components, which are heat and mass exchanger, filters, air handling units (AHUs), fans, and pumps. The capital cost can be calculated using the following equation:24
![]() | (3) |
The levelized annual maintenance cost (MCL) is the cost that occurs during the operation of the cooling system. The MCL is determined by multiplying maintenance during the first year by the levelization factor (LF).24,37
![]() | (4) |
![]() | (5) |
| rn = (1 + rr)(1 + ri) − 1, | (6) |
The levelized annual electricity cost (ELCL) can be calculated using the following eqn (7):25,37
![]() | (7) |
| ELC0 = E × PE, | (8) |
![]() | (9) |
| rn,elc = (1 + rr,Elc)(1 + ri) − 1. | (10) |
The calculation of the real escalation rate of electricity is based on a method provided by the U.S. Bureau of Labor Statistics, which applies the CPI of industry electricity prices.39
The levelized annual CO2 emissions cost (CCL) is an important factor in the decision-making of selecting the proper technology. Considering the socio-environmental perspective and pollution control, it is important to consider the cost of CO2 emissions in the cost analysis. The equation is presented as follows:25
![]() | (11) |
There are many options for carbon pricing across the world; however, the most common types adopted are emission trading systems (ETSs) and carbon taxes. The carbon pricing is based on the average price of 2022. For the unit cost of carbon dioxide emissions in a specific country (PCO2), the equation can be expressed as follows:25
| CCL0 = CDE × E × PCO2, | (12) |
![]() | (13) |
| rn,CO2 = (1 + rr,CO2)(1 + ri) − 1. | (14) |
As of 2022, the Kingdom of Saudi Arabia and the United Arab Emirates have not implemented any carbon pricing mechanisms within their regulatory framework, nor have they instituted a carbon taxation system or a cap-trade emission trading scheme.
In this work, we propose to consider salvage income (SIL) in the levelized annuity method to improve accuracy. The salvage income was substituted into the economic assessment, defined using the following equation:7,8
![]() | (15) |
The cost analysis parameters and data for the selected cities are presented in supplemental materials (Table S6). To improve accuracy, the average discount rate of the year is adopted. Moreover, the inflation rate and the real escalation rate are considered the 5 year average rate, as the electricity price changed a lot in 2022 due to the energy crisis and wars. The lifetime of cooling systems is set at 15 years. In this research, all currencies are converted into USD, and the average exchange rate in 2022 is adopted.40
500 tons annually, including 3500 tons per month in July and August. The results suggest the significant environmental benefits of the hybrid system, especially in high-demand periods. Chen et al.13 applied the hybrid system in Riyadh for human comfort on a representative day of July and found that the IEC component contributed approximately 60% of the total cooling load, achieving a 50% energy saving compared to a conventional system. The differences in the IEC unit contribution and energy savings within the IEC + MVC system between the two studies are attributed to variations in application, operational settings, and climate conditions. These works reveal that the hybrid IEC + MVC cooling method provides a more sustainable alternative to traditional systems.
A comparison of the levelized annual cost of cooling energy (LACOC) indicates that the IEC + MVC system presents economic advantages over the MVC system. Specifically, the levelized annual total cost (LACOCtot) of the IEC + MVC system is $3.1 million, which is significantly less than $4.51 million for the MVC system. Furthermore, the levelized cost of cooling energy (LCOC) of the hybrid system is $18 USD per MWh, which is notably lower than $39.2 USD per MWh for the MVC system. The above results with both economic metrics reveal the economic efficiency of the hybrid system.
Existing studies refer to cost analysis in cooling systems and widely apply the life cycle cost analysis metric. Based on the above results, it can be observed that the levelized annual cost of cooling (LACOC) metric can be used as a refinement and a complementary metric for existing studies in the cost analysis of cooling systems. Moreover, the levelized cost showed the equivalent annual payment and levelized unit cost, which is more intuitive and can compare various technologies fairly when systems have different scales and lifetimes. Additionally, decision-makers of engineering projects commonly need to consider an annual budget plan; the levelized annual cost metric is a more suitable option.
![]() | ||
| Fig. 3 (a) Jeddah comparison of energy consumption. (b) Jeddah energy saving. (c) Jeddah CO2 emission reduction in the arid zone. (d) London comparison of energy consumption. (e) London energy saving. (f) London CO2 emission reduction in the warm temperate zone. (g) Seoul comparison of energy consumption. (h) Seoul energy saving. (i) Seoul CO2 emission reduction in the cold zone. (j) Köppen–Geiger climate zone distribution map of three locations.34,41,42 | ||
London was selected to represent Zone C (Thot > 10 and 0 < Tcold < 18),34 which corresponds to the temperate climate, providing insights into system performance under mild temperatures, without dry seasons (precipitation is relatively evenly distributed throughout the year). Fig. 3d illustrates the energy consumption of primary cooling requirement in warm summer (Taver > 19.5). Fig. 3e shows that the IEC unit provides 100% of the cooling load in London from May to September, saving 1.3 GWh and 1 GWh in July and August, respectively. London's summer low humidity (average 8.7 g kg−1) allows for full IEC part contribution in cooling requirement.
Seoul was chosen to represent Zone D (Thot > 10 and Tcold ≤ 0),34 which falls under the cold climate category, allowing for the assessment of the system operated in cold temperature but with a hot summer (Thot ≥ 22).34 The hybrid system in Seoul achieves 20.6% for the whole year, saving 1 GWh and 1.2 GWh of energy in June and September, respectively. With a hot summer (Taver > 25) but high humidity (average 15.3 g kg−1), Seoul saves 3.7% and 9.5% of energy in July and August, respectively (Fig. 3h). Fig. 3c, f and i illustrate the monthly CO2 emission reduction in the 3 cities. The geographical locations of Jeddah, London and Seoul are depicted in Fig. 3j. The remaining observed cities are shown in Fig. S2, S3 and 2.
The hybrid system presents annual energy saving with IEC part contributions for all cities, as depicted in Fig. 4a. IEC part contributes 100% to satisfy cooling requirements and save energy in Riyadh (41.3 GWh), Madrid (14.1 GWh) and London (2.6 GWh). The hybrid IEC + MVC system demonstrates strong performance in Riyadh, which represents cities located in the arid zone with hot temperatures (Taver > 31 from Mar to Nov, Tsummer > 34), along with low humidity from Mar to Nov (average 5.7 g kg−1). Moreover, the hybrid system performs well in both Madrid and London, which are representative cities located in the temperate zone characterized by hot (Thot ≥ 22)34 or warm summers (not hot summer and Tmon10 ≥ 4).34 Madrid experiences a dry summer climate, whereas London, despite its overall without a dry season (precipitation is relatively evenly distributed throughout the year) climate profile, maintains relatively low humidity (average 8.7 g kg−1) during the warm summer (Taver > 19.5) period when cooling demand arises. Conversely, the hybrid system demonstrates weak performance in Seoul, which is located in the cold zone (Thot > 10 and Tcold ≤ 0),34 representative cities with high humidity from Jul to Sep (average 15.3 g kg−1) despite cooling requirements for hot summer (Taver > 25.2); however, it still presents 24.4% IEC contribution and 20.6% energy saving (3.8 GWh) compared to the conventional system.
The CO2 emission reduction for the hybrid system, as shown in Fig. 4b, highlights a significant CO2 reduction across all observed cities. Cities located in Zone B (low rainfall or mean annual precipitation <10 × Pthreshold)34 classified as an arid climate zone, with the feature of desert (W) and hot temperature (h) (Taver > 31 from Mar to Nov, Tsummer > 34), presented the highest CO2 reductions. Riyadh achieves an 84% reduction (23.55k tons) in humidity from Mar to Nov (average 5.7 g kg−1), Jeddah achieves a 50% reduction (18.74k tons) in humidity from Mar to Nov (average 14.8 g kg−1), and Dubai achieves a 51.20% reduction (12.43 k tons) in humidity from Mar to Nov (average 14.4 g kg−1).
London is located in Zone C (Thot > 10 and 0 < Tcold < 18),34 without a dry season (f: precipitation is relatively evenly distributed throughout the year) and warm summer (b). With cooling requirements in warm summer (Taver > 19.5) and low humidity (average 8.7 g kg−1), the hybrid system reduces CO2 emissions by 675 tons. Seoul, located in cold Zone D (Thot > 10 and Tcold ≤ 0),34 with a hot summer (Taver > 25) but high humidity (average 15.3 g kg−1) achieves a 21% reduction (1.7k tons).
The hybrid system has a strong performance in energy saving and CO2 reduction across all selected cities, particularly strong in hot (Taver > 31 from Mar to Nov, Tsummer > 34) and dry (average 5.7 g kg−1) climate, such as those found in Zone B and temperate regions with hot (Taver > 25) or warm summer (Taver > 19.5), typical of Zone C. Conversely, cities with a cold climate (Zone D) or higher humidity, even during hot summer, presented less IEC component contribution and energy saving percentage. This limitation arises from the limited capacity of the IEC component to manage high humidity. These findings are consistent with Chen et al.'s research,13 which indicated that the IEC unit operates more efficiently under a hot, arid climate, with effectiveness diminishing in humid regions.
The meaning of Pthreshold is clarified by the Köppen–Geiger climate classification system. The perception threshold (Pthreshold) varies according to the seasonal distribution of rainfall: if more than 70% of the mean annual precipitation occurs in winter, Pthreshold = 2 × mean annual temperature; if more than 70% of the mean annual precipitation occurs in summer, then Pthreshold = 2 × mean annual temperature + 28; and otherwise Pthreshold = 2 × MAT + 14.34 Moreover, Thot is the temperature of the hottest month, Tcold is the temperature of the coldest month, and Tmon10 is the number of months when the temperature is above 10.34
Moreover, the highest cost savings with the hybrid IEC + MVC system appeared in Madrid (53.2%) and London (52.4%), which are located in Zone C. These two cities have higher electricity prices and greater IEC contributions. Due to the significant energy savings from the hybrid system in both cities, these energy savings contribute to substantial cost reductions. This underscores the urgent need to improve efficiency and reduce energy consumption in these countries.
Although cities in Zone B (Riyadh, Jeddah, and Dubai) achieved the most energy savings, their energy costs are competitive, and there is no carbon cost in Saudi Arabia and Dubai. The cost savings in Riyadh, Jeddah and Dubai are 32.8%, 18.3% and 22.2%, respectively. In Seoul, Beijing and Windsor (located in Zone D), the electricity price and carbon price are considerably lower than in London and Madrid. Notably, the electricity price in Windsor is one-third of that in London. Although the IEC + MVC system achieved energy saving in the three cities, specifically achieving 68.5% energy saving in Windsor, the cost savings in electricity and carbon costs are insufficient to offset the high capital cost of the hybrid system from a lifetime levelized cost perspective. Thus, the hybrid IEC + MVC system results in higher overall costs in the three cities.
Even though Fig. 4b shows significant CO2 reductions in Riyadh, Jeddah, and Dubai, substantial cost savings for CO2 reduction are observed in almost all cities except these three (Fig. 4e). Madrid shows the highest cost savings for CO2 reduction due to significant energy savings and the highest CO2 pollution costs in Spain among the eight countries. Cities in Zone B have the lowest LCOC of hybrid IEC + MVC systems, with 19.2 USD per MWh, 21 USD per MWh, and 23.2 USD per MWh in Riyadh, Jeddah and Dubai, respectively. Cities in Zone C generally have a higher levelized cost of cooling (LCOC) compared to Zones D and B. However, in Zone D, Seoul, Beijing and Windsor have higher costs for the hybrid system compared to the conventional system (Fig. 4f).
The distribution of cost components in the levelized cost of cooling (LCOC) changes with the transition from MVC to the hybrid IEC + MVC system. With the hybrid IEC + MVC system, capital costs become the largest component; the energy cost percentage decreased significantly in all the observed cities. Notably, the percentage decreased by 47% in London, Riyadh and Madrid. Additionally, the carbon cost percentage is reduced with the hybrid system.
| Variable | Central assumption | Sensitivity range |
|---|---|---|
| CAPCL | Variable | ±10% |
| MCL | Variable | ±10% |
| ELCL | Variable | ±10% |
| CCL | Variable | ±10% |
| SIL | Variable | ±5% |
| Lifetime (n) | 15 years | ±5 years |
![]() | ||
| Fig. 5 (a) Illustration of sensitivity variables analysis for (b) London, (c) Beijing, and (d) Riyadh. | ||
The results of the sensitivity analysis of London, Beijing and Riyadh are shown in Fig. 5b–d, with average LCOC of $272.2 per MWh, $58.6 per MWh, and $19.2 per MWh, respectively. Adjusting the system lifetime had the most significant impact, changing LCOC by up to $76 per MWh in London, $15.9 per MWh in Beijing, and $7 per MWh in Riyadh. The system lifetime presented an asymmetric response in LCOC due to its non-linear features. A five-year reduction in system lifetime increased LCOC by $76 per MWh in London (Fig. 5b), while adding five years increased it by $10 per MWh.
In Beijing (Fig. 5c), a five-year reduction in system lifetime increased LCOC by $15.9 per MWh, while adding five years decreased it by $7.21 per MWh in LCOC. In Riyadh (Fig. 5d), a five-year reduction increased LCOC by $6.7 per MWh, and adding five years decreased it by $3.2 per MWh. CAPCL significantly impacts LCOC, with changes of $20.79 per MWh in London, $4.5 per MWh in Beijing and $1.7 per MWh in Riyadh. ELCL has a moderate impact, with a variation of $6.8 per MWh in London, $1.4 per MWh in Beijing, and $0.3 per MWh in Riyadh. MCL, CCL, and SIL showed relatively small impacts. Notably, the inclusion of the parameter “salvage income” (SIL) in this study has a greater impact on the LCOC than the parameter “maintenance cost” (MCL). This further underscores the importance of the salvage income (SIL) parameter and its value in enhancing the accuracy of LCOE cost assessments. Therefore, incorporating this parameter into future levelized cooling cost assessment studies is essential.
Based on this conversion, the levelized annual cost (LACOC) of the conventional MVC system reported in the existing research was USD 5,299,820.
In comparison, the levelized annual cost (LACOC) of the conventional MVC system in a data centre in Seoul assessed in this study is USD 4
096
674 when using the same parameters as those employed by Cho et al.32 Moreover, this study involved salvage income, yielding a final levelized annual cost (LACOC) of USD 3
999
463.
Despite a difference of approximately 20%, the findings of the two studies are aligned when considering the following differences in the two studies:
(1) The significant difference between the two studies is the temperature and humidity settings, influenced by updated ASHRAE standards. In Cho et al.'s research,32 the indoor temperature and humidity are 22 °C and 50%, respectively. However, in this study, the indoor temperature and humidity are 27 °C and 70% based on ASHRAE 2021, respectively. Energy consumption is significantly reduced due to differences in temperature and humidity.
(2) Salvage income is considered in this research, contributing to the reduced costs within the same city.
(3) The different years of weather data were collected, and the weather data used in this research were collected in 2022, while Cho et al.32 used data from 2017 or earlier.
By comparison, this study conducted a full-year analysis, thereby providing the results for seasonal climate variability. Therefore, the hybrid IEC + MVC system achieved greater annual energy saving at 49% in Jeddah and 84% in Riyadh in a data centre.
The cooling demand and operation conditions for human comfort and data centre are markedly different; the direct comparison of cost results is inappropriate. To enable a meaningful comparison, a cost saving ratio as a normalized metric is employed. A previous study showed approximately 16% cost savings in Jeddah and 35% cost savings in Riyadh. The corresponding data in this study is 18% cost saving in Jeddah and 33% cost saving in Riyadh.
Strong consistency in cost savings is observed despite significant differences in operational characteristics and scale, demonstrating its superiority over the conventional MVC system in diverse application scenarios. This performance consistency validates both the generalizability of the hybrid IEC + MVC system and the reliability of the levelized annual cost model.
The hybrid IEC + MVC system demonstrated energy saving, particularly for cities observed in Zone B with arid and hot (Taver > 31 from Mar to Nov; Tsummer > 34) climates. Significant energy savings were recorded in Riyadh (41.3 GWh), Jeddah (32.9 GWh), and Dubai (31.1 GWh) over the entire year. With relatively strong performance in observed cities in Zone C, temperate regions with hot (Taver > 25) or warm summer (Taver > 19.5), such as London and Madrid. Conversely, the selected cities with cold climates (Zone D) or higher humidity, even during hot summers, presented less IEC component contribution and energy saving percentage, such as Seoul. The IEC unit operates more efficiently under a hot, arid climate; however, its effectiveness diminishes in humid regions due to its limited moisture removal capacity.
The observed cities located in Zones B and C demonstrated cost savings with the hybrid system. Cities with higher electricity prices and greater IEC contributions, such as London and Madrid, exhibited a higher percentage of cost savings, specifically above 52–53%. Sensitivity analysis was conducted for London, Beijing, and Riyadh, revealing that factors such as system lifetime, capital cost, and electricity cost significantly impact the levelized cost of cooling (LCOC). Additionally, “salvage income (SIL)” has a greater impact on the LCOC than the parameter “maintenance cost (MCL)”. This work is expected to set a new course for future levelized cooling cost assessment studies and encompass the cost analysis for the cooling system in an accurate and dynamic fashion.
However, there are some potential barriers to implementation. As the performance of IEC is highly sensitive to ambient humidity, although the hybrid system with the support of MVC, the performance of the IEC + MVC system depends on the climate situation, thereby indicating that the performance cannot be ensured in regions with low ambient temperature and high ambient humidity. Moreover, the implementation of the hybrid system in water-scarce regions may face barriers, as the IEC part of the system requires water for evaporation to provide cooling.
This study has some limitations, as the environmental impact assessment concentrates on power consumption during operation, which does not include embodied emissions. Additionally, the evaluation of both systems has a limited geographic and climate scope.
Future work will explore the economic feasibility of more cities with hybrid cooling systems, integrating renewable energy sources for electricity supply, which is expected to further decrease the environmental impact. In addition, a comprehensive life cycle analysis over the lifespan is required of the cooling system to assess its environmental impact.
The data supporting the findings of this study are available within the article and its supplementary information (SI) file. Supplementary information is available. See DOI: https://doi.org/10.1039/d5su00696a.