Hygrothermal simulation-informed design of mesoporous desiccants for optimised energy efficiency of mixed mode air conditioning systems

Fernando Sarce Thomann *a, Matthew R. Hall ab, Robert Mokaya c and Lee A. Stevens a
aDivision of Materials, Mechanics and Structures, Faculty of Engineering, University of Nottingham, University Park, Nottingham, NG7 2RD, UK. E-mail: emxfs@nottingham.ac.uk; Tel: +44 (0)115 8467873
bBritish Geological Survey, Environmental Science Centre, Keyworth, Nottingham, NG12 5GG, UK
cSchool of Chemistry, University of Nottingham, University Park, Nottingham, NG7 2RD, UK

Received 9th July 2015 , Accepted 27th July 2015

First published on 27th July 2015


Abstract

This paper describes an optimization technique using hygrothermal numerical modelling to determine an ideal and unknown isotherm in order to inform the design of optimised mesoporous desiccants. Their suitability for passive humidity buffering as well as their impact on energy efficiency was assessed when assisting a mixed mode air-conditioning (AC) system. Three clear stages of water vapour adsorption were found that strongly correspond to the Δw gradient when assessing the kinetics of adsorption and exchange rates for periodic moisture loads. Consistent agreement was found between the latent heat of dehumidification used by the AC system and the desiccant decay time after successive sorption loop cycles. This confirmed the material's suitability for specific applications and was found to be highly sensitive to the portion of the isotherm between φi,Lφi,Uw gradient), compared with full adsorption capacity (total w) when assessing total energy consumption. The experimental results of sorption kinetics appeared to be slightly underestimated between the Δw gradient and the response time to reach equilibrium moisture content (EMC). The major underestimations were found to be consistent with the kinetics of adsorption/desorption when analysing their significance based on w differences. These were largely attributed to a combination of adsorption kinetics (time-response) and adsorption/desorption hysteresis. However, this was not evident when comparing long-term experimental data and numerical estimations for water vapour sorption isotherms, since numerical model accurately predicted them. This suggests that both adsorption kinetics and the scanning curve prediction, within a hysteresis loop, are not accurately represented by current hygrothermal models and are hence a priority for future research.


1 Introduction

Desiccant material performance is typically assessed with respect to isotherm characteristics and target application.1,2 This implies that the criteria for optimisation are dependent upon the thermal and moisture loads, and operating parameters, inside the closed environment being studied. Optimised mesoporous desiccants can be used to passively regulate indoor dry bulb temperature and relative humidity in closed environments, and to reduce the energy penalty of mechanical heating, ventilation and air conditioning (HVAC).3,4 Traditional refrigerant vapour compressor systems (VCS) used for regulating the interior psychrometric conditions of ‘closed environments’ (e.g., offices, hospitals, laboratories, industry, etc.) are responsible for a large amount of energy consumption with associated greenhouse gas emissions.5–8 The study of desiccants as dehumidifier materials in the air-conditioning (AC) industry has attracted the interest of many researchers in the last decades.9–13 This has primarily motivated the understanding their abilities to reduce the ‘energy penalties’ caused by mechanical air dehumidification (latent heat), and the required energy to reheat the air up to the supply air temperature (sensible heat), by engineering their water adsorption/retention properties.14–17 Some examples of desiccant implementation are included in (i) AC mixed mode systems,18,19 (ii) evaporative cooling technology for high humidity climates,20,21 (iii) regulating indoor thermal comfort,22–24 (iv) as a solid-desiccant in solar AC systems,25–28 (v) indirect evaporative cooling systems,29,30 and (vi) waste heat transformation applications for absorption chillers and heat pumps.31–34

As an alternative to traditional VCS cooling technologies, solid-desiccant cooling systems (SDC) have motivated the investigation of advanced desiccant materials since their characteristics (water adsorption behaviour, regeneration capacity, and long-term stability) play an important role in their performance and efficiency.35,36 These have been organized into three main categories:37 (i) composite desiccants (i.e., silica-based, mesoporous silicate-based and carbon-based), (ii) nanoporous inorganic materials (i.e., aluminosilicate zeolites, aluminophosphates, and aerogels), and (iii) polymeric desiccants (i.e., metal-organic frameworks (MOFs) and polyelectrolyte). Ongoing research38–42 has been focused on the preparation of these materials with improved water adsorption characteristics which include high surface area, large pore volume and an unprecedented physicochemical variability. This, in the case of MCM-41 and SBA-15, has been possible due to the modulation of their textural properties through the synthesis process by controlling temperature43,44 and reaction time.45,46 These mesoporous materials exhibit enhanced water adsorption properties compared with those traditional silica-based as a result of having regular pore structures and high surfaces areas.47 On the other hand, significant interest has been focussed on MOFs as water adsorbents due to their large adsorption capacity, fine-tunable pore size, high surface area, and pore volume controlled by change in organic ligands and metal sub-units.48–51 In recent work done by Furukawa et al.,52 large water adsorption capacity and pore volume (735–850 cm3 g−1 and 0.88 cm3 g−1, respectively) was reported from low to high pv/p0 range (0.05–0.7). Their MOF materials exhibited outstanding sorption/desorption water uptake after 5 cycles (showing no loss of porosity) at a low regeneration temperature (25 °C). In addition, studies done in Materials of Institute Lavoisier (MIL) frameworks showed even greater values of water adsorption (1.06–1.7 cm3 g−1) and large pore volume (1.4–1.58 cm3 g−1)53–55 with low regeneration temperature (30 °C), and rapid-response rates of 40% weight loss after only 30 minutes at 30 °C.55 It is expected that desirable properties in an optimal desiccant material are therefore not only its water adsorption capacity (and isotherm type), but also their rate of sorption/desorption (kinetic stability) at a defined regeneration temperature.

All of these desiccants have currently only been analysed in terms of full adsorption capacity (i.e., independent of isotherm shape) with the intention of producing large pore volumes, and have not assessed their suitability for specific applications. In order to do this an understanding of the isotherm shape at particular pv/p0 ranges is required, as well as their transient response to changes in ambient vapour pressure, Δpv. If understood, advanced desiccant materials could then be used to partially or even fully regulate the fluctuations of RH and to allow reduction in energy penalties when tailoring and optimizing their isotherm shape for regulating ‘specific’ psychrometric requirements of closed environments. Therefore, the aim of this study was to apply a numerical hygrothermal approach (from our previous work56) to determine the ideal (and unknown) water vapour isotherm to inform the design of optimised mesoporous desiccants. The isotherms were then experimentally re-created through synthesis and modulation of well-known mesoporous material classes (MCM-41 and SBA 15). The material's suitability for regulating indoor RH, in terms of dehumidification load reductions (enthalpy), were assessed after different moisture loads had been introduced. They were then assessed to enable the relative effect on energy efficiency when assisting a mixed mode air conditioning (AC) system. The sorption/desorption kinetic response of selected traditional and advanced desiccants will be then assessed experimentally.

2 Experimental section

2.1. Desiccant candidates

A set of ten candidate desiccants (see Fig. 1) were selected as part of a representative group of mesoporous materials, as defined by IUPAC.57 The aim was to assess their capacity for buffering humidity ratio fluctuations (and hence indoor air enthalpy) within specific closed environment scenarios. In recent work a principle was established which defined the available moisture capacity, Δw for RH buffering within a specific operating range.56 Therefore, the region of interest among the isotherm candidates was defined between point b seen in Fig. 2a (1st inflection point; the onset of multilayer physisorption) and point c (2nd inflection point; the percolation threshold). The capillary transport coefficients (Dws and Dww) were calculated from each isotherm,58 and the water adsorption coefficient, A was assumed constant for all materials based on assumptions established from previous work.38
image file: c5ta05162b-f1.tif
Fig. 1 Water vapour sorption isotherms for all desiccant candidates. References are provided for the following desiccants candidates: MIL-101,66 PS-C16-R,67 KIT-1 and FSM-16,69 MCM-41@150 and 180,56 aerogel.68 The three water vapour isotherms from the new materials made (MCM-41@165, SBA-15 6 nm and 10 nm) are also provided.

image file: c5ta05162b-f2.tif
Fig. 2 (a) Schematic representation of a water vapour sorption isotherm portions at different EMC stages a–b, b–c and c–d. (b) Corresponding water vapour sorption kinetics at different EMC stages a–b, b–c and c–d that shows EMC in the segments 1, 2 and 3.

2.2. Synthesis and characterization

Synthesis and the textural properties of the pure silica MCM-41@165 were obtained using same experimental description of our previous work.56 Synthesis of SBA-15 (6 nm pore size) was prepared in a similar manner to Zhao et al.59 with the same batch of SBA-15 used throughout the study. Pluronic 123 (P123, triblock copolymer (EO)20(PO)70(EO)20, 80.0 g) was dissolved in aqueous hydrochloric acid (1.33 M, 3000 ml) with vigorous stirring at 35 °C. After complete dissolution tetraethoxyorthosilicate (TEOS, 182 ml) was added dropwise and the mixture stirred at 35 °C for 24 h. The solution was then statically heated at 85 °C for 48 h. The resulting white solid was dried in an oven at 105 °C for 2 h before heating in a furnace to 600 °C for 6 h to obtain a white solid powder. Synthesis of SBA-15 (10 nm pore size) was prepared in a similar manner to Zhao et al.59 with the same batch of SBA-15 used throughout the study. Pluronic 123 (P123, triblock copolymer (EO)20(PO)70(EO)20, 4.0 g) was dissolved in aqueous hydrochloric acid (1.33 M, 75 ml) and mesitylene (2 ml) with vigorous stirring at 35 °C. After complete dissolution tetraethoxyorthosilicate (TEOS, 4.55 ml) was added dropwise and the mixture stirred at 35 °C for 24 h. The solution was then placed in a Teflon lined autoclave and heated at 120 °C for 24 h. The resulting white solid was recovered and then in an oven at 105 °C for 2 h before heating in a furnace at 600 °C for 6 h to obtain a white solid powder. Textural properties (see Table 1) were determined from N2 sorption analysis at −196 °C using a Micromeritics ASAP 2020 analyser. Samples (approximately 0.2 g) were outgassed prior to analysis under high vacuum at 120 °C for 15 h. Specific surface areas (SSA) was calculated using the standard Brunauer–Emmett–Teller (SBET) method, micropore volume (Vm) by the t-plot method with Harkins and Jura correction for thickness curve correction. Average pore diameter (Dp) was determined by the Barrett–Joyner–Halenda (BJH) method by applying a cylindrical pore model using Kelvin equation with Harkins and Jura for thickness curve correction. Nitrogen adsorption at relative pressure of 0.99 was taken as total pore volume (Vp).
Table 1 Textural properties summary for SBA-15 desiccant candidates
Sample S BET/m2 g−1 V m/cm3 g−1 V p/cm3 g−1 D p/nm
SBA-15 6 nm 876 0.17 0.91 5.7
SBA-15 10 nm 757 0.12 1.26 10.2


2.3. Dynamic vapour sorption (DVS)

A gravimetric dynamic vapour sorption (DVS) test was performed to determine the water vapour isotherms for the candidate materials (MCM-41@165, SBA-15 6 nm and SBA-15 10 nm). A DVS Advantage-2 series (Surface Measurements Systems Ltd, London, England) with incorporated ultra-microbalance (1 μg sensitivity) and fully automated weighing/purging was used to independently control Tdb and RH to an accuracy of ±0.5 K and ±1.5%, respectively (vapour pressure accuracy ±1.5% pv/p0). Advantage Control Software (ACS) was used to automatically record the data in 1 min time-steps. Before analysis, the samples were dried under vacuum at 120 °C for 12 h to ensure removal of residual moisture. In order to ensure stability for baseline measurements accuracy, clean quartz sample and reference pan were left to fully equilibrate at 23 °C at constant nitrogen flow (10 sccm 1 bar) for 1 h prior to the weighing and tared. Dry samples (approximately 0.2 g) were weighed into the sample pan and allowed to equilibrate again under the carrier gas for 1 h. After stability, the sample weight was recorded (initial mass M0) and reference weight was set to zero with no counter weight. To ensure w = 0, a pre-heating sequence was set from to 23 to 150 °C (2 °C min−1 ramp rate) for 1 h prior to vapour dosing. A targeted relative vapour pressure from φ = 0.05 to 1 (φ = 0.05 intervals) was programmed to sequentially increase in a 21-steps full cycle (sorption/desorption), where a change in mass step (0.001% per min) was set until EMC was achieved. This was performed at Tdb 23 °C and to a constant water vapour flow rate of 100 sccm.

Three sets of experiments to assess the water vapour adsorption/desorption kinetics were performed. For this, a set of RH limits were defined (20–30%; 30–50%; and 50–70%) and the kinetics of the moisture sorption began to sequentially fluctuate in an adsorption/desorption cycle. Each cycle comprised 2 h of moisture sorption (i.e., 30–50% RH) followed by 2 h of moisture desorption (i.e., 50–30% RH) for a total period of 12 h (3 complete cycles). Prior to testing, all samples were outgassed under vacuum at 120 °C for 12 h and the pre-heating sequence was applied as described above. To ensure that EMC was achieved for the w20, w30 and w50 set points, all samples were pre-conditioned within the DVS chamber before the cycles started. Taring and equilibration of the microbalance steps were done as previously described, where all samples (∼0.02 g) were loaded to define the initial mass (M0) in the DVS. This was performed at Tdb 23 °C at a constant water vapour flow rate of 100 sccm, as with previous experiments.

2.4. Hygrothermal numerical model

A number of hygrothermal models packages have been validated over the past 15+ years against experimental data including (but not limited to) DELPHIN, HAM, MATCH and WUFI, as part of the Annex 41 project.60 To validate numerical model predictions for heat and mass transport/storage physical model are commonly used to simulate the bulk-scale of the hygrothermal behaviour of some functional material properties.61–63 As a minimum, all hygrothermal numerical models must accurately predict the following bulk-scale coupled phenomena of heat and mass transport/storage:64

• Heat storage in dry materials and any absorbed water.

• Heat transport by moisture-dependent thermal conduction.

• Latent heat transfer by vapour diffusion.

• Moisture storage by vapour sorption and capillary forces.

• Moisture transport by vapour diffusion.

• Moisture transport by liquid transport (surface diffusion and capillary flow).

For this study, the Wärme und Feuchte Instationär (WUFI) hygrothermal numerical model,65 WUFI+ v2.5.3 (Fraunhofer, Germany), was used. The governing equation that represents the moisture storage function is seen in the LHS of eqn (1), which is proportional to the derivative of the water adsorption isotherm (∂w/∂φ). The transport terms on the RHS of eqn (1) are described by the divergence of liquid and vapour diffusion with phase changes strongly dependent on the moisture fields and fluxes. Whilst the driving potential for vapour flux, which is vapour pressure (pv = φ × psat), is strongly temperature-dependent (saturation pressure psat ∼ exp(T)). The liquid flow, on the other hand, is governed by differences in capillary forces which are assumed to be a function of RH only (i.e., from Kelvin condensation). The storage term seen in LHS of eqn (2) describes the vapour enthalpy of air flow inside the closed environment, whilst the RHS describes heat transport due to solid conduction and diffusion of heat associated with the specific enthalpy of vapour water.

 
image file: c5ta05162b-t1.tif(1)
 
image file: c5ta05162b-t2.tif(2)

2.5. Sensitivity analysis

Sensitivity analysis was conducted to assess the water vapour adsorption behaviour (capacity) and water vapour exchange performance for all candidate materials in a closed environment where the initial moisture content was w = 0. The hygrothermal numerical model was setup to sequentially perform water vapour adsorption simulations between the operating limits φmin = 0 and φmax = 0.95. A moisture generation rate of 3 g h−1 per 24 h period with and an air infiltration rate of 0.35 ACH h−1 were set. The water vapour exchange rate was then estimated as the fraction of cumulative moisture load per hour. The closed environment comprised a thermally and hygrically isolated box (where V = 1 m3) with the initial boundary conditions (interior/exterior) were set at φi = 0 and φe = 0.95 under isothermal conditions, Tdb = 23 °C. The fabric of the envelope comprised a 2 mm thick vapour barrier (Sd = 1500 m) and 240 mm thick vacuum insulation panel (λ = 0.001). A non-visualized internal component was defined (area/volume ratio = 0.4048 m2, equivalent to ∼500 g) comprising 2 mm thickness of candidate material and using the hygrothermal functional properties detailed in Table 2. These were gathered from previous research,38 where pore geometry and specific surface area were obtained using the BJH and BET method with N2 physisorption. Validation against high resolution transmission electron microscopy (HRTEM) and small-angle X-ray diffraction (SAXRD) were conducted. Modified transient plane source (MTPS), differential scanning calorimetry (DSC) and dynamic vapour sorption techniques were used to determine the hygrothermal functional properties. The numerical model was solved using (i) increased accuracy and adapted convergence options, (ii) time step 1 min, ‘fine’ mesh grid spacing, and (iii) calculation accuracy of 0.5%/0.5 °C for RH and Tdb, respectively.
Table 2 Hygrothermal functional properties for mesoporous silica. *Values taken from ref. 38
Material n (m3 m−3) ϕ pore (nm) ρ b (kg m−3) C p (J kg−1 K−1) λ (W m−1 K−1) A (kg m−2 s−0.5) μ (−)
MS-8.3* 0.76 8.3 618 1691 0.05 0.550 10.52


2.6. Parametric studies

Parametric hygrothermal simulations were conducted to determine the fluctuation of φ(t) and the candidate material's capacity for humidity buffering in a series of closed environment scenarios. Each material was parametrically assessed against five pairs of operating limits (φminφmax); i.e., 0.4–0.5; 0.5–0.6; 0.6–0.7; 0.7–0.8; 0.8–0.9. The initial moisture content, w was set according to the φmin limit at EMC; i.e., w40, w50, w60, w70, and w80. A number of moisture loading cycles, N was set comprising 12 h moisture generation (at a rate of 3 g h−1) followed by 12 h of no moisture generation (24 h total), i.e., 22 cycles in total. The air infiltration rate (0.35 ACH h−1) and φe were constant, with the latter value determined according to the φmin limit (i.e., φe = 0.4, 0.5, 0.6, 0.7, or 0.8) and to a constant dry bulb temperature, Tdb = 23 °C. The non-visualized component thickness and area/volume ratio, fabric components, and parameters for the numerical model were set as described in Section 2.4. Expanded numerical simulations were then conducted to quantify the operational energy used for dehumidification loads (enthalpy energy) and cooling demand, with the candidate materials assisting a mixed mode AC system. The upper indoor dry bulb temperature set point, (Tdbi,U) was set as Tdbi ≥ 25 °C, and the upper indoor air humidity set point (φmax) was defined for each pair of operating limits (φi ≥ 0.5, 0.6, 0.7, 0.8, 0.9), as previously described. In order to simulate instantaneous control response, 50 kg h−1 of dehumidification capacity and 50 kW cooling capacity were assumed for the AC system. Once the φmax and Tdbi,U set points had been achieved, and if any of the operational limits were exceeded, the ratio of dehumidification or cooling demand could be estimated and the relative effect on energy efficiency calculated. This commonly occurred in cases where the moisture loads were always positive, i.e., where no infiltration of air at lower relative moisture content occurred. For each candidate material, the initial value of w was set according to the φmin limit, i.e., EMC at w40, w50, w60, w70, and w80. A constant air infiltration rate (0.35 ACH h−1) was used, and the moisture load was derived from the resultant outdoor air moisture content at φe = 0.95 at Tdb = 23 °C. The non-visualized component thickness and area/volume ratio, fabric components, and parameters for the numerical model were set as described in Section 2.4. The initial boundary conditions were, however, set equally for interior operating limits (φminφmax), and φe = 0.95 at Tdb = 23 °C. The numerical model setup was later adjusted to simulate the kinetics of the water vapour uptake by sequentially fluctuating the adsorption/desorption cycle across an arbitrary sixty cycles (N = 60). Each material was parametrically assessed using the same RH limits as for the DVS experiments in Section 2.2 (20–30%; 30–50%; and 50–70%), where the initial w was set accordingly (i.e., EMC at w20, w30 and w50) and Tdb = 23 °C. A constant ACH = 20.37 h−1 and area/volume ratio (0.01) of the non-visualized component were determined. This was to enable scaling between the DVS chamber volume (Vch = 0.0002945 m3) and the numerical model (V = 1 m3), assuming an infiltration rate of 100 sccm (0.006 m3 h−1) and material quantity of 0.02 g. This enabled validation of the numerical model against the DVS experiments.

3 Results and discussion

3.1. Continuous moisture load sensitivity analysis

Fig. 3 clearly shows three stages of water vapour adsorption as w reaches equilibrium moisture content (EMC), where each stage was identified within a specific portion of the isotherm as depicted in Fig. 2a. The first stage (schematically sketched in Fig. 2b) between points a and b represents an early saturation stage of the materials in the first 48 h where a steep φ gradient was found. In the cases of MIL-101,66 PS-C16-R67 and SBA-15, the higher Δw gradient during adsorption between φ = 0 to ca. 0.4, and desorption between 0 to ca. 0.9 resulted in a less pronounced curve and a small but significant delay when achieving the 1st inflection point b. A second stage was a sub-plateau between point b and c where a characteristic stabilized φi corresponded to the highest Δw at the 2nd inflection point c, i.e., the percolation threshold. The slope of the sub-plateau indicates its dependency upon the steepness of the w: pv/p0 gradient corresponding to maximum pore volume. Previous work has demonstrated that the positive correlation between the moisture storage capacity (Δw) and the optimum φ operating range for a given isotherm can also be identified.56 Almost all samples exhibited the sub-plateau segment in their isotherms, which started from point b (onset of multilayer physisorption between φ = ca. 0.35–0.90), with the exception of the aerogel.68 This suggests a prolonged capillary conduction stage. In the third stage between points c and d, a rapid increase in φi was observed with noticeable variation towards EMC100, especially in materials having type V isotherms (e.g., KIT-1 (ref. 69)). The progressive reduction in pore volume strongly affected the time taken to reach inflection point d towards EMC100, as a consequence of the low Δw on that portion of the isotherm. Evidence of this was found for MCM-41@180,56 which was the first to achieve EMC100 (112 h) and has the lowest pore volume (0.53 g cm−3). However, it was apparent that by having a greater Δw between points c and d, the elapsed time before reaching EMC100 was significantly increased. Evidence of this was found when comparing KIT-1 (152 h) and FSM-16 (168 h),69 both with similar Δw at point c (460 kg m−3), but with the latter having a steep w: pv/p0 gradient resulting in a higher Δw above φ = 0.7 (∼44 kg m−3).
image file: c5ta05162b-f3.tif
Fig. 3 Water vapour sorption kinetic stages for all desiccant candidates when achieving EMC100. Initial w = 0 for all desiccant materials and the moisture load applied is the moisture content of the infiltrated air at ACH = 0.35−1, where φe = 0.95.

3.2. Water vapour exchange performance

Fig. 4 shows the cumulative water vapour uptake for all candidate materials. The same correlations were observed in Section 3.1 for stage 1–3 water vapour adsorption and the corresponding portions of the isotherm (see Fig. 2). It appears that in the first stage (points a and b) there is an ‘apparent’ high initial water vapour uptake (relative to w = 0) followed by a visible depression caused by early saturation. This applied to MCM-41, KIT-1, FSM-16, and aerogel. Note that in the cases of MIL-101, PS-C16-R and SBA-15 the cumulative water vapour adsorption was clearly higher (between 84% to 99%) and controlled by the higher initial Δw gradient between points a and b (see Fig. 2a). After this stage, a sub-plateau was observed in the second stage (points b and c, with the highest Δw gradient), which corresponded to maximum pore volume. Here some materials (MIL-101, PS-C16-R and SBA-15) reached 100% of the cumulative water vapour uptake. Once point c of the isotherm was reached the moisture content (with respect to pore volume) was sufficiently high for performance to begin to decay after successive internal moisture load cycles. This indicates moisture content dependency and reduced water vapour adsorption ability prior to reaching w100 from point c of the isotherm. Fig. 5a shows a positive linear correlation between the moisture storage capacity, w and the water vapour being exchanged (against time) with the absorbent. However, Fig. 5b shows that the relationship between w and the time taken to exceed the φmax limit (φ = 0.95) correlates more strongly with type V isotherms (R2 = 0.99) compared with type III isotherms (R2 = 0.77). This could partially be explained by the observation that the process of water vapour adsorption was triggered early by a capillary condensation stage on type III isotherms. Therefore, SBA-15 10 nm and aerogel material do not fit trend line A since their capillary potential and capacity for water vapour adsorption are already lowered.
image file: c5ta05162b-f4.tif
Fig. 4 Cumulative water vapour uptake for all desiccant candidates. Initial w = 0 for all desiccant materials and the moisture load applied is the moisture content of the infiltrated air at ACH = 0.35−1, where φe = 0.95.

image file: c5ta05162b-f5.tif
Fig. 5 (a) Linear correlation between the moisture storage capacity, w and the water vapour being exchanged. (b) Relationship between total moisture storage capacity and time taken to achieve EMC100.

3.3. Water vapour buffering simulations

Fig. 6a and b shows the RH buffering results for repeated long-term loop cycling (at N = 12) of all material candidates. The operating range (φminφmax) of each test was 0.4–0.5 and 0.7–0.8, respectively. The absence of water vapour buffering can be seen followed by an early decay process which correlates to the first stage of water vapour adsorption between points a and b of the isotherm (Fig. 2a). This sudden decay relates to the smaller Δw gradient seen in Fig. 7a, causing the material to fail after N number of cycles when the fluctuation of φ(t) exceeds the φmax limit (Fig. 7b). From Fig. 7b it is apparent that the progressive decay until material failure corresponds with the largest proportion of water vapour adsorption (see Fig. 7a) in each operating range. The most suitable candidate materials for each range can be identified as that with the longest time before exceeding the φmax limit. This suggests that the sub-plateau segment (see y-axis displacement in Fig. 3) is sensitive both to x-axis adjustments in the sorption isotherm (i.e., pore size distribution) and to the value of Δw (w: pv/p0 gradient) between φi,Lφi,U limits.
image file: c5ta05162b-f6.tif
Fig. 6 RH buffering results for all desiccant candidates, where the number of cycles, N = 12. (a) Shows the simulations results for RH buffering between 40–50%, and (b) 70–80% operating ranges. The red-dotted lines correspond to the maximum and minimum RH limits.

image file: c5ta05162b-f7.tif
Fig. 7 (a) Water vapour uptake capacity at different Δw for all desiccant candidates (Δw = 40–50; 50–60; 60–70; 70–80; and 80–90). (b) Time taken for all desiccant materials when the fluctuation of φ(t) exceeds the φmax limit; where Δw = 40–50; 50–60; 60–70; 70–80; and 80–90. This also correspond to the threshold when the materials reaches failure at the number of cycles, N = 60.

3.4. Air dehumidification and energy consumption

Fig. 8a–c show the ratio of dehumidification loads removed by the materials once they achieve the φmax set point on the mixed mode AC system (repeated for ranges between: 40–50; 60–70; and 70–80% RH). The steepness of the curve was found to be dependent on the time required to achieve the corresponding EMC (e.g., EMC50 as seen in Fig. 8a). This supports the idea that total control (100%) from the AC system corresponds to the lower Δw gradient, whereas a plateau (at 0%) means that the indoor moisture load was fully regulated by the desiccant by having a higher Δw gradient. In all cases, it can be recognized that a higher elapsed time before the inflection of the curve start there is a corresponding material that fits within the optimum operating ranges; for example, MIL-101 and PS-C16-R (φ = 0.4–0.5), MCM-41@150,56 KIT-1, and FSM-16 (φ = 0.6–0.7), and all MCM-41 types (φ = 0.7–0.8). Once the inflection point starts (above 0%; see red circles in Fig. 8a) in the sub-plateau region, the adsorbent progressively has lower potential to fully regulate φi and air dehumidification starts to operate.
image file: c5ta05162b-f8.tif
Fig. 8 Dehumidification ratio performed by the AC system and the desiccant candidates according to the operating ranges (a) 40–50; (b) 60–70; and (c) 70–80% RH. Here, 0% indicates that the desiccant candidate is fully regulating indoor RH. Above 0% indicates that the AC system start to working in truly mixed mode. The time taken for reaching EMC at the corresponding operating ranges are solely dependent upon the Δw gradient.

Fig. 9 shows a significant difference between the resultant indoor RH(t) and the material's RH(t) in all simulations. Since the adsorbent appears not to have achieved EMC (i.e., EMC50–70–80) a distinctive offset between both curves was observed. This suggests that the material may continue adsorbing water vapour whilst the φmin set point on the AC is still dehumidifying the indoor air, and hence working in true mixed mode.


image file: c5ta05162b-f9.tif
Fig. 9 Comparison between the resultant indoor RH(t) and the material's RH(t) at different operating ranges for desiccant materials MIL-101, FSM-16 and MCM-41@165. The offset dotted-lines represent the progressive indoor air saturation towards equilibrium with the desiccant at the respective ACH−1. The total number of cycles, N = 22 and the red circles represents when the desiccants have been reached EMC at the corresponding operating RH ranges.

Fig. 10 shows a positive linear correlation between the moisture sorption capacity (Δw gradient) and the latent heat used for air dehumidification for each specific operational range. This satisfactorily proves that passive regulation of RH fluctuations in a specific closed environment can fully be controlled by materials where a higher Δw gradient is found whilst consuming less energy. This was previously evidenced in Fig. 8a–c, where reduction of the dehumidification loads removed by the AC system was strongly related to a higher Δw gradient corresponding to materials that fit within the optimum operating ranges. Consistent agreement was also observed between the decay (up to material failure) and the latent heat of dehumidification, wherein the most suitable candidate materials can be identified in Fig. 7b. A significant increment in the resultant indoor air temperature was observed in some cases (e.g., MIL-101 and PS-C16-R), most likely due to heat of adsorption. As a result, an extra cooling load was added to both MIL-101 and PS-C16-R (i.e., 0.22 and 0.16 KW respectively) in order to maintain isothermal conditions (Tdbi = 23 °C). Fig. 11 shows the total energy used for air dehumidification (latent heat) and the energy used for cooling purposes (Fig. 11a), and no correlation trend (R2 = 0.2706) between total moisture storage, w and total latent heat for air dehumidification (Fig. 11b). In the latter case, it can be seen that having higher w (e.g. aerogel, MIL-101, PS-C16-R and SBA-15 10 nm) does not result in lowering the energy used for dehumidification purposes when assuming total pore volume capacity. Evidence of this can be seen when comparing the total latent heat used for type V and type III isotherms; e.g., MCM-41@180 (1.51 kW and w = 369.4 kg m−3) and aerogel (1.65 kW and w = 754.8 kg m−3), with the latter having w ∼ 2 times higher compared to MCM-41@180. These results provide evidence for the premise in which adsorbents are expected to fully operate under total adsorption capacity, independent of isotherm shape, rather than for specific applications and pv/p0 scenarios.


image file: c5ta05162b-f10.tif
Fig. 10 Correlation between moisture sorption capacity and the latent heat used for air dehumidification from the AC system at the corresponding operating ranges (40–50%; 50–60%; 60–70%; 70–80%; 80–90%). Each trend line correspond to the aggrupation of all desiccant candidates when performing the air dehumidification through the AC system.

image file: c5ta05162b-f11.tif
Fig. 11 (a) Total energy used for air dehumidification for all desiccant candidates. In the case of materials MIL-101 and PS-C16-R, a cooling demand is represented by the hatched box above the values. (b) Non-linear correlation between total moisture storage, w and total latent heat for air dehumidification. Type III isotherms can clearly be recognized as the precursors of this non-linear trend as their total moisture content, w do not correlate with the total energy used for air dehumidification and cooling loads, resulting in R2 = 0.2706.

3.5. Experimental work and model validation

Fig. 12 compares the experimental DVS and numerical simulations (water vapour sorption/desorption kinetics) for the three newly synthesised materials (MCM-41@165, SBA-15 6 nm and SBA-15 10 nm). The upper and lower % RH buffering limits were defined as 20–30% RH; 30–50% RH; and 50–70% RH in Fig. 12. Experimentally, it appears that for all materials EMC (red dotted line in Fig. 12) was achieved at N = 3 for cases where the Δw gradient was sufficiently small (a, b, d, e, and g) with respect to the relevant portion of each sorption isotherm (see Fig. 1). Additionally, it appears that the kinetics for sorption/desorption within the % RH buffering limits was highly sensitive to the Δw gradient. This corresponded to a rapid response (steep adsorption/desorption curve) for the smallest Δw gradient. Evidence of this was found in MCM-41@165 operating at 20–30 and 30–50% RH (see red boxes in Table 3). In all other cases it was evidenced by a less steep sorption/desorption curve and corresponding to those with a higher Δw gradient. To some extent, the numerical predictions seen in Fig. 12(a, b, d, e, and g) appear to be slightly underestimated (solid black line) towards the time in achieving EMC, especially in those between Δw20–50 (see Table 3). This is normally found in numerical models due to the lack of a dynamic input for w, with respect to the time-response for water vapour adsorption at partial EMC; i.e., w inputs are assumed to be at full EMC for single sorption isotherms. Further analysis confirmed that the average difference (%) between experimental and numerical w data for all sorption cycles was significantly attributed to this; e.g., MCM-41@165 with 43.4% within the Δw30–50 cycle seen in Table 4. In the case of those having greater w between the upper and lower % RH buffering limits (c, f, h, and i from Fig. 12), it is suggested that for both experimental and numerical data, their capacity for water vapour adsorption is significantly beyond the required time period for achieving EMC (see Table 3). Besides, for all candidates seen in red circles (Fig. 12), there appears to be a combination of time-response together with a hysteresis phenomenon. The latter, can be recognized by the highest average (%) values at the end of the third cycle shown in Table 4 (see a, c, d, and g). In both adsorption and desorption cycles, this could be largely due to the presence of scanning curves within the hysteresis loop. However, the corresponding loops at this stage are unidentified. Conversely, there is close agreement (full sorption/desorption reversibility) when a smaller Δw gradient is found; for example, SBA-15 10 nm operating in the 50–70% RH ranges (see Fig. 12i). This could be explained because SBA-15 10 nm showed the lowest average difference between experimental and numerical w data (see Table 4 – 7.6%), which indicates a high degree of sorption/desorption reversibility (and small hysteresis −4.6%). On the other hand, numerical data of the final EMC were accurately predicted (refer to Section 3.1), suggesting that there is some level of variance between short and long periods for water vapour adsorption/desorption kinetics. This perhaps indicates a need for further research in which the concept of time-response for water vapour adsorption, hysteresis loops and the associated scanning curves can be fully implemented by the current state-of-the-art hygrothermal numerical models.
image file: c5ta05162b-f12.tif
Fig. 12 Water vapour sorption/desorption kinetics comparison between experimental DVS and numerical simulations. The results are deemed to be read horizontally, where (A) indicates the operating range ΔRH = 20–30%; (B) ΔRH = 30–50%; and (C) ΔRH = 50–70%. The red-dotted lines indicate achieving the corresponding EMC, whereas the green-dotted lines indicate the base line for the initial w.
Table 3 Moisture storage capacity at different Δw for all new desiccant materials. The time in achieving EMC is also presented with an approximate time (h) for each desiccant at the corresponding ranges: Δw20–30; Δw30–50; and Δw50–70. These time values represent numerical predictions based on w inputs that are assumed to be at full EMC
Desiccant materials Moisture storage at Δw (kg m−3) Time in achieving EMC (∼h)
Δw20–30 Δw30–50 Δw50–70 Δw20–30 Δw30–50 Δw50–70
MCM-41@165 5.4 15.1 69.8 3 5.5 22
SBA-15 6 nm 14.2 28.3 42.5 5 9.5 11
SBA-15 10 nm 16.8 33.1 41.8 6 11 11


Table 4 Average difference (%) between experimental and numerical w data for all new mesoporous desiccant materials, when modelling for each independent RH buffering scenario 20–30% RH; 30–50% RH; and 50–70% RH. The w differences are provided for the following ranges: Δw20–30; Δw30–50; and Δw50–70, denoted with the vowels (a–i) according to Fig. 12, and for the three completed adsorption/desorption cycles
Cycles Mesoporous desiccant materials
MCM-41@165 SBA-15 6 nm SBA-15 10 nm
Δw20–30 Δw30–50 Δw50–70 Δw20–30 Δw30–50 Δw50–70 Δw20–30 Δw30–50 Δw50–70
a b c d e f g h i
Ads. cycle 1 44.4% 43.3% 48.4% 44.4% 43.6% 39.8% 40.0% 35.2% 27.8%
Des. cycle 1 11.3% −56.6% 28.2% 16.9% 6.5% 13.0% 24.9% 1.7% 3.0%
Ads. cycle 2 48.8% 40.5% 45.9% 38.2% 32.2% 28.6% 33.1% 18.5% 11.5%
Des. cycle 2 29.4% −27.9% 41.8% 21.3% 7.3% 12.0% 23.2% −3.7% −4.2%
Ads. cycle 3 51.8% 43.4% 52.4% 38.1% 33.4% 29.0% 32.7% 16.6% 7.6%
Des. cycle 3 36.3% −15.0% 49.2% 23.9% 11.0% 14.8% 24.1% −3.7% −4.6%


4 Conclusions

Three new mesoporous desiccant materials (MCM-41@165, SBA-15 6 nm and SBA-15 10 nm) were successfully synthesised with pore size modulation, in order to experimentally recreate the ideal isotherms determined (for differing applications) by the hygrothermal model optimization technique previously developed by the authors. A series of numerical simulations were performed to assess the desiccants' capacity for regulating indoor RH and the corresponding impact on energy efficiency when assisting a mixed mode AC system. The simulated results clearly showed three stages of water vapour adsorption that strongly related to the Δw gradient showing a positive linear correlation with the latent heat used for air dehumidification. The results were also consistent with the predictions for progressive decay and the point of failure, indicating the suitability of the materials for the pv/p0 scenarios for which they had been designed. Increasing w did not result in lowering the energy used for dehumidification purposes, especially for the type III isotherm materials, and found no correlation (R2 = 0.2706) between total moisture storage, w and total latent heat for air dehumidification. Experimental DVS and numerical simulation for water vapour sorption/desorption kinetics were conducted for the three new materials, in which the latter appeared to be slightly underestimated. This was consistent for most desiccants shown in Fig. 12 and Table 4, where the lack of a dynamic input for w (time-response for water vapour adsorption), caused significant differences between both results. Additionally, Table 4 showed (see a, c, d, and g) that the major underestimations were largely attributed to a combination of adsorption kinetics (time-response) and hysteresis. This, for the case of MCM-41@165, was found to account for 52.4% (average) of the total w values at the third RH buffering cycle. Conversely, it was found that the numerical model accurately predicted EMC and found very good agreement with the experimental data taken from the water vapour isotherm. Further research is therefore needed for coupling both adsorption kinetics (i.e., adsorption time-response) and realistic scanning curve estimates within the hysteresis loop.

Nomenclature

ρ Bulk density kg m−3
C p Specific heat capacity J kg−1 K−1
λ(w)Moisture-dependent thermal conductivity W m−1 K−1
φ Relative vapour pressure (pv/psat)
n Bulk porosity m3 m−3
w = f(φ)Water vapour sorption isotherm kg m−3
μ(φ)Water vapour diffusion factor
D w(w)Liquid water diffusivity m2 s−1
RHRelative humidity; where RH = φ × 100%
p v/p0Partial pressure of water vapour
H Total enthalpy J m−3
h v Latent heat of phase change J kg−1
t Time s
T Temperature K
δ p Vapour permeability kg m−1 s−1 Pa

Suffixes

iinterior
eexterior
Llower limit
Uupper limit

Acknowledgements

The authors wish to gratefully acknowledge the support of CONICYT for funding this research through the ‘Programa de Formación de Capital Humano Avanzado, BECAS CHILE’ – Ministerio de Educación, Gobierno de Chile.

References

  1. W. A. Belding, M. P. F. Delmas and W. D. Holeman, Appl. Therm. Eng., 1996, 16, 447–459 CrossRef CAS.
  2. J. D. Chung and D.-Y. Lee, Int. J. Refrig., 2009, 32, 720–726 CrossRef CAS PubMed.
  3. S. P. Casey, M. R. Hall, S. C. E. Tsang and M. A. Khan, Build. Environ., 2013, 60, 24–36 CrossRef PubMed.
  4. B. F. Yu, Z. B. Hu, M. Liu, H. L. Yang, Q. X. Kong and Y. H. Liu, Int. J. Refrig., 2009, 32, 3–20 CrossRef PubMed.
  5. J. M. Calm, Int. J. Refrig., 2002, 25, 293–305 CrossRef CAS.
  6. J. T. McMullan, Int. J. Refrig., 2002, 25, 89–99 CrossRef CAS.
  7. S. B. Riffat, C. F. Afonso, A. C. Oliveira and D. A. Reay, Appl. Therm. Eng., 1997, 17, 33–42 CrossRef CAS.
  8. G. Lorentzen, Int. J. Refrig., 1995, 18, 190–197 CrossRef CAS.
  9. Adsorption air conditioning system, U.S. Pat., 5 580 369, 1996 Search PubMed.
  10. Desiccant assisted air conditioning system, U.S. Pat., 5 816 065, 1998 Search PubMed.
  11. A. A. Kinsara, M. M. Elsayed and O. M. Al-Rabghi, Appl. Therm. Eng., 1996, 16, 791–806 CrossRef CAS.
  12. Y. J. Dai, R. Z. Wang, H. F. Zhang and J. D. Yu, Appl. Therm. Eng., 2001, 21, 1185–1202 CrossRef CAS.
  13. N. Srivastava and I. Eames, Appl. Therm. Eng., 1998, 18, 707–714 CrossRef CAS.
  14. K. Daou, R. Wang and Z. Xia, Renewable Sustainable Energy Rev., 2006, 10, 55–77 CrossRef CAS PubMed.
  15. D. La, Y. Dai, Y. Li, R. Wang and T. Ge, Renewable Sustainable Energy Rev., 2010, 14, 130–147 CrossRef CAS PubMed.
  16. L. Zhang and J. Niu, Appl. Therm. Eng., 2002, 22, 1347–1367 CrossRef CAS.
  17. N. C. Srivastava and I. W. Eames, Appl. Therm. Eng., 1998, 18, 707–714 CrossRef CAS.
  18. M. O'Kelly, M. E. Walter and J. R. Rowland, Energ. Build., 2015, 86, 45–57 CrossRef PubMed.
  19. P. Dhar and S. Singh, Appl. Therm. Eng., 2001, 21, 119–134 CrossRef CAS.
  20. S. Jain, P. Dhar and S. Kaushik, Int. J. Refrig., 1995, 18, 287–296 CrossRef CAS.
  21. J. Camargo, E. Godoy Jr and C. Ebinuma, J. Braz. Soc. Mech. Sci. Eng., 2005, 27, 243–247 CrossRef.
  22. P. Mazzei, F. Minichiello and D. Palma, Appl. Therm. Eng., 2005, 25, 677–707 CrossRef PubMed.
  23. P. Mazzei, F. Minichiello and D. Palma, Appl. Therm. Eng., 2002, 22, 545–560 CrossRef.
  24. Materials for energy efficiency and thermal comfort in buildings, ed. M. R. Hall, CRC Press, Cambridge, 2010 Search PubMed.
  25. G. Panaras, E. Mathioulakis and V. Belessiotis, Energy, 2011, 36, 2399–2406 CrossRef PubMed.
  26. G. Grossman, Sol. Energy, 2002, 72, 53–62 CrossRef CAS.
  27. C. A. Balaras, G. Grossman, H.-M. Henning, C. A. I. Ferreira, E. Podesser, L. Wang and E. Wiemken, Renewable Sustainable Energy Rev., 2007, 11, 299–314 CrossRef CAS PubMed.
  28. A. E. Kabeel, Renewable Energy, 2007, 32, 1842–1857 CrossRef CAS PubMed.
  29. M. Steeman, A. Janssens and M. de Paepe, Appl. Therm. Eng., 2009, 29, 2870–2875 CrossRef PubMed.
  30. M. Goldsworthy and S. White, Int. J. Refrig., 2011, 34, 148–158 CrossRef PubMed.
  31. S. Henninger, F. Schmidt and H.-M. Henning, Appl. Therm. Eng., 2010, 30, 1692–1702 CrossRef CAS PubMed.
  32. F. Ziegler, Int. J. Refrig., 2002, 25, 450–459 CrossRef.
  33. R. Z. Wang and R. G. Oliveira, Prog. Energy Combust. Sci., 2006, 32, 424–458 CrossRef PubMed.
  34. H. Demir, M. Mobedi and S. Ülkü, Renewable Sustainable Energy Rev., 2008, 12, 2381–2403 CrossRef PubMed.
  35. J. Nie, L. Fang, G. Zhang, Y. Sheng, X. Kong, Y. Zhang and B. W. Olesen, Build. Environ., 2015, 85, 233–242 CrossRef PubMed.
  36. E. Hürdoğan, O. Büyükalaca, M. T. Balta, A. Hepbasli and T. Yılmaz, Energy Convers. Manage., 2013, 69, 9–16 CrossRef PubMed.
  37. X. Zheng, T. Ge and R. Wang, Energy, 2014, 74, 280–294 CrossRef PubMed.
  38. M. R. Hall, S. C. E. Tsang, S. P. Casey, M. A. Khan and H. Yang, Acta Mater., 2012, 60, 89–101 CrossRef CAS PubMed.
  39. S. T. Meek, J. A. Greathouse and M. D. Allendorf, Adv. Mater., 2011, 23, 249–267 CrossRef CAS PubMed.
  40. H. Furukawa, N. Ko, Y. B. Go, N. Aratani, S. B. Choi, E. Choi, A. Ö. Yazaydin, R. Q. Snurr, M. O'Keeffe and J. Kim, Science, 2010, 329, 424–428 CrossRef CAS PubMed.
  41. R. Banerjee, A. Phan, B. Wang, C. Knobler, H. Furukawa, M. O'Keeffe and O. M. Yaghi, Science, 2008, 319, 939–943 CrossRef CAS PubMed.
  42. J. L. C. Rowsell and O. M. Yaghi, Microporous Mesoporous Mater., 2004, 73, 3–14 CrossRef CAS PubMed.
  43. W. Sangchoom and R. Mokaya, J. Mater. Chem., 2012, 22, 18872–18878 RSC.
  44. A. Corma, Q. Kan, M. T. Navarro, J. Pérez-Pariente and F. Rey, Chem. Mater., 1997, 9, 2123–2126 CrossRef CAS.
  45. A. Sayari and S. Hamoudi, Chem. Mater., 2001, 13, 3151–3168 CrossRef CAS.
  46. J. Lei, J. Fan, C. Yu, L. Zhang, S. Jiang, B. Tu and D. Zhao, Microporous Mesoporous Mater., 2004, 73, 121–128 CrossRef CAS PubMed.
  47. R. Collier, T. Cale and Z. Lavan, Advanced desiccant materials assessment, Enerscope, Inc, Glendale, AZ (USA), 1986 Search PubMed.
  48. J. Canivet, A. Fateeva, Y. Guo, B. Coasne and D. Farrusseng, Chem. Soc. Rev., 2014, 43(16), 5594–5617 RSC.
  49. P. Küsgens, M. Rose, I. Senkovska, H. Fröde, A. Henschel, S. Siegle and S. Kaskel, Microporous Mesoporous Mater., 2009, 120, 325–330 CrossRef PubMed.
  50. J. Ehrenmann, S. K. Henninger and C. Janiak, Eur. J. Inorg. Chem., 2011, 2011, 471–474 CrossRef PubMed.
  51. S. K. Henninger, H. A. Habib and C. Janiak, J. Am. Chem. Soc., 2009, 131, 2776–2777 CrossRef CAS PubMed.
  52. H. Furukawa, F. Gándara, Y.-B. Zhang, J. Jiang, W. L. Queen, M. R. Hudson and O. M. Yaghi, J. Am. Chem. Soc., 2014, 136, 4369–4381 CrossRef CAS PubMed.
  53. A. Khutia, H. U. Rammelberg, T. Schmidt, S. Henninger and C. Janiak, Chem. Mater., 2013, 25, 790–798 CrossRef CAS.
  54. G. Akiyama, R. Matsuda, H. Sato, A. Hori, M. Takata and S. Kitagawa, Microporous Mesoporous Mater., 2012, 157, 89–93 CrossRef CAS PubMed.
  55. Y. K. Seo, J. W. Yoon, J. S. Lee, Y. K. Hwang, C. H. Jun, J. S. Chang, S. Wuttke, P. Bazin, A. Vimont and M. Daturi, Adv. Mater., 2012, 24, 806–810 CrossRef CAS PubMed.
  56. F. S. Thomann, M. R. Hall, W. Sangchoom and R. Mokaya, Microporous Mesoporous Mater., 2015, 211, 113–123 CrossRef PubMed.
  57. J. Rouquerol, F. Rouquerol and K. S. W. Sing, Absorption by powders and porous solids, Academic press, Marseille, 1998 Search PubMed.
  58. H. M. Künzel, Ph.D. Thesis, IRB-Verlag, 1995.
  59. D. Zhao, J. Feng, Q. Huo, N. Melosh, G. H. Fredrickson, B. F. Chmelka and G. D. Stucky, Science, 1998, 279, 548–552 CrossRef CAS.
  60. M. Woloszyn and C. Rode, Build. Simulat. Int. J., 2008, 1, 5–24 CrossRef.
  61. T. Kalamees and J. Vinha, Build. Environ., 2003, 38, 689–697 CrossRef.
  62. Z. Pavlík and R. Černý, Energ. Build., 2008, 40, 673–678 CrossRef PubMed.
  63. H. M. Künzel, A. Holm, D. Zirkelbach and A. N. Karagiozis, Sol. Energy, 2005, 78, 554–561 CrossRef PubMed.
  64. B. EN, German version DIN EN, 2007, 15026.
  65. Fraunhofer, WUFI Pro & Plus®: PC-Program for coupled heat and mass transfer in building components, http://www.wufi.de/index_e.html, (accessed 28/07/2015).
  66. S. K. Henninger, F. Jeremias, H. Kummer and C. Janiak, Eur. J. Inorg. Chem., 2012, 2012, 2625–2634 CrossRef CAS PubMed.
  67. H. Naono, M. Hakuman, T. Tanaka, N. Tamura and K. Nakai, J. Colloid Interface Sci., 2000, 225, 411–420 CrossRef CAS PubMed.
  68. Z. Knez and Z. Novak, J. Chem. Eng. Data, 2001, 46, 858–860 CrossRef CAS.
  69. W. Wang, L. Wu, Z. Li, Y. Fang, J. Ding and J. Xiao, Drying Technol., 2013, 31, 1334–1345 CrossRef CAS PubMed.

This journal is © The Royal Society of Chemistry 2015